375 Amp Cable Size at 350 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 375 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 12.16V (2.93%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 20.06V (4.83%)
Voltage at Load402.8 VLine Loss: 7899.6 W
Max Power & Breaker269.55 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3243.27 V (781.51%)0.0 V5349.87 V (1289.13%)2106562.5 WDrop High
2.5 mm²24 A18 A1945.96 V (468.91%)0.0 V3209.92 V (773.48%)1263937.5 WDrop High
4 mm²32 A25 A1216.22 V (293.07%)0.0 V2006.2 V (483.42%)789960.9 WDrop High
6 mm²41 A32 A810.82 V (195.38%)0.0 V1337.47 V (322.28%)526640.6 WDrop High
10 mm²57 A44 A486.49 V (117.23%)0.0 V802.48 V (193.37%)315984.4 WDrop High
16 mm²76 A59 A304.06 V (73.27%)110.9 V501.55 V (120.86%)197490.2 WDrop High
25 mm²101 A78 A194.6 V (46.89%)220.4 V320.99 V (77.35%)126393.7 WDrop High
35 mm²125 A97 A139.0 V (33.49%)276.0 V229.28 V (55.25%)90281.2 WDrop High
50 mm²151 A118 A97.3 V (23.45%)317.7 V160.5 V (38.67%)63196.9 WDrop High
70 mm²192 A150 A69.5 V (16.75%)345.5 V114.64 V (27.62%)45140.6 WDrop High
95 mm²232 A181 A51.21 V (12.34%)363.8 V84.47 V (20.35%)33261.5 WDrop High
120 mm²269 A210 A40.54 V (9.77%)374.5 V66.87 V (16.11%)26332.0 WDrop High
150 mm²309 A241 A32.43 V (7.82%)382.6 V53.5 V (12.89%)21065.6 WDrop High
185 mm²353 A275 A26.3 V (6.34%)388.7 V43.38 V (10.45%)17080.2 WDrop High
240 mm²415 A324 A20.27 V (4.88%)394.7 V33.44 V (8.06%)13166.0 W~ ≤5%
300 mm²477 A372 A16.22 V (3.91%)398.8 V26.75 V (6.45%)10532.8 W~ ≤5%
400 mm²570 A445 A12.16 V (2.93%)402.8 V20.06 V (4.83%)7899.6 W✓ OK (≤3%)

FAQ — 375 Amp Cable Size at 350 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 375A at 350 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 375A over 350m at 415V (voltage drop: 12.16V or 2.93%).

What is the power capacity of 375A at 415V?

At unity power factor, 375A at 415V supports 269.55 kW with a standard 400A circuit breaker.