400 Amp Cable Size at 400 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 400 A over 400 m (1312.3 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 7.42V (1.78%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 24.46V (5.89%)
Voltage at Load407.6 VLine Loss: 5136.0 W
Max Power & Breaker287.52 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 400A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3953.69 V (952.7%)0.0 V6521.75 V (1571.51%)2739200.0 WDrop High
2.5 mm²24 A18 A2372.22 V (571.62%)0.0 V3913.05 V (942.9%)1643520.0 WDrop High
4 mm²32 A25 A1482.64 V (357.26%)0.0 V2445.66 V (589.31%)1027200.0 WDrop High
6 mm²41 A32 A988.42 V (238.17%)0.0 V1630.44 V (392.88%)684800.0 WDrop High
10 mm²57 A44 A593.05 V (142.9%)0.0 V978.26 V (235.73%)410880.0 WDrop High
16 mm²76 A59 A370.66 V (89.32%)44.3 V611.41 V (147.33%)256800.0 WDrop High
25 mm²101 A78 A237.22 V (57.16%)177.8 V391.3 V (94.29%)164352.0 WDrop High
35 mm²125 A97 A169.44 V (40.83%)245.6 V279.5 V (67.35%)117394.3 WDrop High
50 mm²151 A118 A118.61 V (28.58%)296.4 V195.65 V (47.15%)82176.0 WDrop High
70 mm²192 A150 A84.72 V (20.41%)330.3 V139.75 V (33.68%)58697.1 WDrop High
95 mm²232 A181 A62.43 V (15.04%)352.6 V102.97 V (24.81%)43250.5 WDrop High
120 mm²269 A210 A49.42 V (11.91%)365.6 V81.52 V (19.64%)34240.0 WDrop High
150 mm²309 A241 A39.54 V (9.53%)375.5 V65.22 V (15.72%)27392.0 WDrop High
185 mm²353 A275 A32.06 V (7.72%)382.9 V52.88 V (12.74%)22209.7 WDrop High
240 mm²415 A324 A24.71 V (5.95%)390.3 V40.76 V (9.82%)17120.0 WDrop High
300 mm²477 A372 A19.77 V (4.76%)395.2 V32.61 V (7.86%)13696.0 W~ ≤5%
400 mm²570 A445 A14.83 V (3.57%)400.2 V24.46 V (5.89%)10272.0 W~ ≤5%

FAQ — 400 Amp Cable Size at 400 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 400A at 400 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 400A over 400m at 415V (voltage drop: 7.42V or 1.78%).

What is the power capacity of 400A at 415V?

At unity power factor, 400A at 415V supports 287.52 kW with a standard 400A circuit breaker.