425 Amp Cable Size at 150 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 150 m (492.1 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 7.88V (1.9%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 9.74V (2.35%)
Voltage at Load407.1 VLine Loss: 5798.1 W
Max Power & Breaker305.49 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1575.3 V (379.59%)0.0 V2598.51 V (626.15%)1159612.5 WDrop High
2.5 mm²24 A18 A945.18 V (227.75%)0.0 V1559.11 V (375.69%)695767.5 WDrop High
4 mm²32 A25 A590.74 V (142.35%)0.0 V974.44 V (234.81%)434854.7 WDrop High
6 mm²41 A32 A393.83 V (94.9%)21.2 V649.63 V (156.54%)289903.1 WDrop High
10 mm²57 A44 A236.3 V (56.94%)178.7 V389.78 V (93.92%)173941.9 WDrop High
16 mm²76 A59 A147.68 V (35.59%)267.3 V243.61 V (58.7%)108713.7 WDrop High
25 mm²101 A78 A94.52 V (22.78%)320.5 V155.91 V (37.57%)69576.7 WDrop High
35 mm²125 A97 A67.51 V (16.27%)347.5 V111.36 V (26.83%)49697.7 WDrop High
50 mm²151 A118 A47.26 V (11.39%)367.7 V77.96 V (18.78%)34788.4 WDrop High
70 mm²192 A150 A33.76 V (8.13%)381.2 V55.68 V (13.42%)24848.8 WDrop High
95 mm²232 A181 A24.87 V (5.99%)390.1 V41.03 V (9.89%)18309.7 WDrop High
120 mm²269 A210 A19.69 V (4.74%)395.3 V32.48 V (7.83%)14495.2 WDrop High
150 mm²309 A241 A15.75 V (3.8%)399.2 V25.99 V (6.26%)11596.1 WDrop High
185 mm²353 A275 A12.77 V (3.08%)402.2 V21.07 V (5.08%)9402.3 WDrop High
240 mm²415 A324 A9.85 V (2.37%)405.2 V16.24 V (3.91%)7247.6 WDrop High
300 mm²477 A372 A7.88 V (1.9%)407.1 V12.99 V (3.13%)5798.1 W✓ OK (≤3%)
400 mm²570 A445 A5.91 V (1.42%)409.1 V9.74 V (2.35%)4348.5 W✓ OK (≤3%)

FAQ — 425 Amp Cable Size at 150 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 425A at 150 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 425A over 150m at 415V (voltage drop: 7.88V or 1.9%).

What is the power capacity of 425A at 415V?

At unity power factor, 425A at 415V supports 305.49 kW with a standard 450A circuit breaker.