425 Amp Cable Size at 200 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 200 m (656.2 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 10.5V (2.53%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 12.99V (3.13%)
Voltage at Load404.5 VLine Loss: 7730.7 W
Max Power & Breaker305.49 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 200m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2100.4 V (506.12%)0.0 V3464.68 V (834.86%)1546150.0 WDrop High
2.5 mm²24 A18 A1260.24 V (303.67%)0.0 V2078.81 V (500.92%)927690.0 WDrop High
4 mm²32 A25 A787.65 V (189.8%)0.0 V1299.25 V (313.07%)579806.2 WDrop High
6 mm²41 A32 A525.1 V (126.53%)0.0 V866.17 V (208.72%)386537.5 WDrop High
10 mm²57 A44 A315.06 V (75.92%)99.9 V519.7 V (125.23%)231922.5 WDrop High
16 mm²76 A59 A196.91 V (47.45%)218.1 V324.81 V (78.27%)144951.6 WDrop High
25 mm²101 A78 A126.02 V (30.37%)289.0 V207.88 V (50.09%)92769.0 WDrop High
35 mm²125 A97 A90.02 V (21.69%)325.0 V148.49 V (35.78%)66263.6 WDrop High
50 mm²151 A118 A63.01 V (15.18%)352.0 V103.94 V (25.05%)46384.5 WDrop High
70 mm²192 A150 A45.01 V (10.85%)370.0 V74.24 V (17.89%)33131.8 WDrop High
95 mm²232 A181 A33.16 V (7.99%)381.8 V54.71 V (13.18%)24412.9 WDrop High
120 mm²269 A210 A26.26 V (6.33%)388.7 V43.31 V (10.44%)19326.9 WDrop High
150 mm²309 A241 A21.0 V (5.06%)394.0 V34.65 V (8.35%)15461.5 WDrop High
185 mm²353 A275 A17.03 V (4.1%)398.0 V28.09 V (6.77%)12536.4 WDrop High
240 mm²415 A324 A13.13 V (3.16%)401.9 V21.65 V (5.22%)9663.4 WDrop High
300 mm²477 A372 A10.5 V (2.53%)404.5 V17.32 V (4.17%)7730.7 W✓ OK (≤3%)
400 mm²570 A445 A7.88 V (1.9%)407.1 V12.99 V (3.13%)5798.1 W✓ OK (≤3%)

FAQ — 425 Amp Cable Size at 200 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 425A at 200 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 425A over 200m at 415V (voltage drop: 10.5V or 2.53%).

What is the power capacity of 425A at 415V?

At unity power factor, 425A at 415V supports 305.49 kW with a standard 450A circuit breaker.