425 Amp Cable Size at 600 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 600 m (1968.5 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 11.81V (1.71%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 38.98V (5.65%)
Voltage at Load678.2 VLine Loss: 8697.1 W
Max Power & Breaker507.92 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A6301.2 V (913.22%)0.0 V10394.04 V (1506.38%)4638450.0 WDrop High
2.5 mm²24 A18 A3780.72 V (547.93%)0.0 V6236.42 V (903.83%)2783070.0 WDrop High
4 mm²32 A25 A2362.95 V (342.46%)0.0 V3897.76 V (564.89%)1739418.8 WDrop High
6 mm²41 A32 A1575.3 V (228.3%)0.0 V2598.51 V (376.6%)1159612.5 WDrop High
10 mm²57 A44 A945.18 V (136.98%)0.0 V1559.11 V (225.96%)695767.5 WDrop High
16 mm²76 A59 A590.74 V (85.61%)99.3 V974.44 V (141.22%)434854.7 WDrop High
25 mm²101 A78 A378.07 V (54.79%)311.9 V623.64 V (90.38%)278307.0 WDrop High
35 mm²125 A97 A270.05 V (39.14%)419.9 V445.46 V (64.56%)198790.7 WDrop High
50 mm²151 A118 A189.04 V (27.4%)501.0 V311.82 V (45.19%)139153.5 WDrop High
70 mm²192 A150 A135.03 V (19.57%)555.0 V222.73 V (32.28%)99395.4 WDrop High
95 mm²232 A181 A99.49 V (14.42%)590.5 V164.12 V (23.78%)73238.7 WDrop High
120 mm²269 A210 A78.77 V (11.42%)611.2 V129.93 V (18.83%)57980.6 WDrop High
150 mm²309 A241 A63.01 V (9.13%)627.0 V103.94 V (15.06%)46384.5 WDrop High
185 mm²353 A275 A51.09 V (7.4%)638.9 V84.28 V (12.21%)37609.1 WDrop High
240 mm²415 A324 A39.38 V (5.71%)650.6 V64.96 V (9.41%)28990.3 WDrop High
300 mm²477 A372 A31.51 V (4.57%)658.5 V51.97 V (7.53%)23192.2 W~ ≤5%
400 mm²570 A445 A23.63 V (3.42%)666.4 V38.98 V (5.65%)17394.2 W~ ≤5%

FAQ — 425 Amp Cable Size at 600 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 425A at 600 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 425A over 600m at 690V (voltage drop: 11.81V or 1.71%).

What is the power capacity of 425A at 690V?

At unity power factor, 425A at 690V supports 507.92 kW with a standard 450A circuit breaker.