45 Amp Cable Size at 175 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 45 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 11.68V (2.81%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 9.63V (2.32%)
Voltage at Load403.3 VLine Loss: 910.0 W
Max Power & Breaker32.35 kW45A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A194.6 V (46.89%)220.4 V320.99 V (77.35%)15167.2 WDrop High
2.5 mm²24 A18 A116.76 V (28.13%)298.2 V192.6 V (46.41%)9100.3 WDrop High
4 mm²32 A25 A72.97 V (17.58%)342.0 V120.37 V (29.01%)5687.7 WDrop High
6 mm²41 A32 A48.65 V (11.72%)366.4 V80.25 V (19.34%)3791.8 WDrop High
10 mm²57 A44 A29.19 V (7.03%)385.8 V48.15 V (11.6%)2275.1 WDrop High
16 mm²76 A59 A18.24 V (4.4%)396.8 V30.09 V (7.25%)1421.9 W~ ≤5%
25 mm²101 A78 A11.68 V (2.81%)403.3 V19.26 V (4.64%)910.0 W✓ OK (≤3%)
35 mm²125 A97 A8.34 V (2.01%)406.7 V13.76 V (3.31%)650.0 W✓ OK (≤3%)
50 mm²151 A118 A5.84 V (1.41%)409.2 V9.63 V (2.32%)455.0 W✓ OK (≤3%)
70 mm²192 A150 A4.17 V (1.0%)410.8 V6.88 V (1.66%)325.0 W✓ OK (≤3%)
95 mm²232 A181 A3.07 V (0.74%)411.9 V5.07 V (1.22%)239.5 W✓ OK (≤3%)
120 mm²269 A210 A2.43 V (0.59%)412.6 V4.01 V (0.97%)189.6 W✓ OK (≤3%)
150 mm²309 A241 A1.95 V (0.47%)413.1 V3.21 V (0.77%)151.7 W✓ OK (≤3%)
185 mm²353 A275 A1.58 V (0.38%)413.4 V2.6 V (0.63%)123.0 W✓ OK (≤3%)
240 mm²415 A324 A1.22 V (0.29%)413.8 V2.01 V (0.48%)94.8 W✓ OK (≤3%)
300 mm²477 A372 A0.97 V (0.23%)414.0 V1.6 V (0.39%)75.8 W✓ OK (≤3%)
400 mm²570 A445 A0.73 V (0.18%)414.3 V1.2 V (0.29%)56.9 W✓ OK (≤3%)

FAQ — 45 Amp Cable Size at 175 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 45A at 175 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 45A over 175m at 415V (voltage drop: 11.68V or 2.81%).

What is the power capacity of 45A at 415V?

At unity power factor, 45A at 415V supports 32.35 kW with a standard 45A circuit breaker.