45 Amp Cable Size at 400 Meters (230V Single-Phase (IEC Europe / UK / AU))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 45 A over 400 m (1312.3 ft).

Copper Cable (≤3% Drop)120 mm²Drop: 6.42V (2.79%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 6.87V (2.99%)
Voltage at Load223.6 VLine Loss: 288.9 W
Max Power & Breaker10.35 kW45A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A513.6 V (223.3%)0.0 V847.2 V (368.35%)23112.0 WDrop High
2.5 mm²24 A18 A308.16 V (133.98%)0.0 V508.32 V (221.01%)13867.2 WDrop High
4 mm²32 A25 A192.6 V (83.74%)37.4 V317.7 V (138.13%)8667.0 WDrop High
6 mm²41 A32 A128.4 V (55.83%)101.6 V211.8 V (92.09%)5778.0 WDrop High
10 mm²57 A44 A77.04 V (33.5%)153.0 V127.08 V (55.25%)3466.8 WDrop High
16 mm²76 A59 A48.15 V (20.93%)181.9 V79.42 V (34.53%)2166.7 WDrop High
25 mm²101 A78 A30.82 V (13.4%)199.2 V50.83 V (22.1%)1386.7 WDrop High
35 mm²125 A97 A22.01 V (9.57%)208.0 V36.31 V (15.79%)990.5 WDrop High
50 mm²151 A118 A15.41 V (6.7%)214.6 V25.42 V (11.05%)693.4 WDrop High
70 mm²192 A150 A11.01 V (4.79%)219.0 V18.15 V (7.89%)495.3 W~ ≤5%
95 mm²232 A181 A8.11 V (3.53%)221.9 V13.38 V (5.82%)364.9 W~ ≤5%
120 mm²269 A210 A6.42 V (2.79%)223.6 V10.59 V (4.6%)288.9 W✓ OK (≤3%)
150 mm²309 A241 A5.14 V (2.23%)224.9 V8.47 V (3.68%)231.1 W✓ OK (≤3%)
185 mm²353 A275 A4.16 V (1.81%)225.8 V6.87 V (2.99%)187.4 W✓ OK (≤3%)
240 mm²415 A324 A3.21 V (1.4%)226.8 V5.29 V (2.3%)144.4 W✓ OK (≤3%)
300 mm²477 A372 A2.57 V (1.12%)227.4 V4.24 V (1.84%)115.6 W✓ OK (≤3%)
400 mm²570 A445 A1.93 V (0.84%)228.1 V3.18 V (1.38%)86.7 W✓ OK (≤3%)

FAQ — 45 Amp Cable Size at 400 Meters (230V Single-Phase (IEC Europe / UK / AU))

What mm² cable size is required for 45A at 400 meters (230V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 120 mm² copper cable for 45A over 400m at 230V (voltage drop: 6.42V or 2.79%).

What is the power capacity of 45A at 230V?

At unity power factor, 45A at 230V supports 10.35 kW with a standard 45A circuit breaker.