⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

45 Amp Cable Size at 80 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 45 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)16 mm²Drop: 8.34V (2.01%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 8.8V (2.12%)
Voltage at Load406.7 VLine Loss: 650.0 W
Max Power & Breaker32.35 kW45A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 45A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A88.96 V (21.44%)326.0 V146.74 V (35.36%)6933.6 WDrop High
2.5 mm²24 A18 A53.37 V (12.86%)361.6 V88.04 V (21.22%)4160.2 WDrop High
4 mm²32 A25 A33.36 V (8.04%)381.6 V55.03 V (13.26%)2600.1 WDrop High
6 mm²41 A32 A22.24 V (5.36%)392.8 V36.68 V (8.84%)1733.4 WDrop High
10 mm²57 A44 A13.34 V (3.22%)401.7 V22.01 V (5.3%)1040.0 W~ ≤5%
16 mm²76 A59 A8.34 V (2.01%)406.7 V13.76 V (3.31%)650.0 W✓ OK (≤3%)
25 mm²101 A78 A5.34 V (1.29%)409.7 V8.8 V (2.12%)416.0 W✓ OK (≤3%)
35 mm²125 A97 A3.81 V (0.92%)411.2 V6.29 V (1.52%)297.2 W✓ OK (≤3%)
50 mm²151 A118 A2.67 V (0.64%)412.3 V4.4 V (1.06%)208.0 W✓ OK (≤3%)
70 mm²192 A150 A1.91 V (0.46%)413.1 V3.14 V (0.76%)148.6 W✓ OK (≤3%)
95 mm²232 A181 A1.4 V (0.34%)413.6 V2.32 V (0.56%)109.5 W✓ OK (≤3%)
120 mm²269 A210 A1.11 V (0.27%)413.9 V1.83 V (0.44%)86.7 W✓ OK (≤3%)
150 mm²309 A241 A0.89 V (0.21%)414.1 V1.47 V (0.35%)69.3 W✓ OK (≤3%)
185 mm²353 A275 A0.72 V (0.17%)414.3 V1.19 V (0.29%)56.2 W✓ OK (≤3%)
240 mm²415 A324 A0.56 V (0.13%)414.4 V0.92 V (0.22%)43.3 W✓ OK (≤3%)
300 mm²477 A372 A0.44 V (0.11%)414.6 V0.73 V (0.18%)34.7 W✓ OK (≤3%)
400 mm²570 A445 A0.33 V (0.08%)414.7 V0.55 V (0.13%)26.0 W✓ OK (≤3%)

FAQ — 45 Amp Cable Size at 80 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 45A at 80 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 16 mm² copper cable for 45A over 80m at 415V (voltage drop: 8.34V or 2.01%).

What is the power capacity of 45A at 415V?

At unity power factor, 45A at 415V supports 32.35 kW with a standard 45A circuit breaker.