450 Amp Cable Size at 175 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 450 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 9.73V (2.34%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 12.04V (2.9%)
Voltage at Load405.3 VLine Loss: 7583.6 W
Max Power & Breaker323.46 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 450A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1945.96 V (468.91%)0.0 V3209.92 V (773.48%)1516725.0 WDrop High
2.5 mm²24 A18 A1167.58 V (281.34%)0.0 V1925.95 V (464.09%)910035.0 WDrop High
4 mm²32 A25 A729.73 V (175.84%)0.0 V1203.72 V (290.05%)568771.9 WDrop High
6 mm²41 A32 A486.49 V (117.23%)0.0 V802.48 V (193.37%)379181.2 WDrop High
10 mm²57 A44 A291.89 V (70.34%)123.1 V481.49 V (116.02%)227508.7 WDrop High
16 mm²76 A59 A182.43 V (43.96%)232.6 V300.93 V (72.51%)142193.0 WDrop High
25 mm²101 A78 A116.76 V (28.13%)298.2 V192.6 V (46.41%)91003.5 WDrop High
35 mm²125 A97 A83.4 V (20.1%)331.6 V137.57 V (33.15%)65002.5 WDrop High
50 mm²151 A118 A58.38 V (14.07%)356.6 V96.3 V (23.2%)45501.8 WDrop High
70 mm²192 A150 A41.7 V (10.05%)373.3 V68.78 V (16.57%)32501.2 WDrop High
95 mm²232 A181 A30.73 V (7.4%)384.3 V50.68 V (12.21%)23948.3 WDrop High
120 mm²269 A210 A24.32 V (5.86%)390.7 V40.12 V (9.67%)18959.1 WDrop High
150 mm²309 A241 A19.46 V (4.69%)395.5 V32.1 V (7.73%)15167.2 WDrop High
185 mm²353 A275 A15.78 V (3.8%)399.2 V26.03 V (6.27%)12297.8 WDrop High
240 mm²415 A324 A12.16 V (2.93%)402.8 V20.06 V (4.83%)9479.5 WDrop High
300 mm²477 A372 A9.73 V (2.34%)405.3 V16.05 V (3.87%)7583.6 W✓ OK (≤3%)
400 mm²570 A445 A7.3 V (1.76%)407.7 V12.04 V (2.9%)5687.7 W✓ OK (≤3%)

FAQ — 450 Amp Cable Size at 175 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 450A at 175 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 450A over 175m at 415V (voltage drop: 9.73V or 2.34%).

What is the power capacity of 450A at 415V?

At unity power factor, 450A at 415V supports 323.46 kW with a standard 450A circuit breaker.