450 Amp Cable Size at 250 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 450 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 13.9V (2.01%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 17.2V (2.49%)
Voltage at Load676.1 VLine Loss: 10833.8 W
Max Power & Breaker537.8 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 450A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2779.94 V (402.89%)0.0 V4585.6 V (664.58%)2166750.0 WDrop High
2.5 mm²24 A18 A1667.96 V (241.73%)0.0 V2751.36 V (398.75%)1300050.0 WDrop High
4 mm²32 A25 A1042.48 V (151.08%)0.0 V1719.6 V (249.22%)812531.2 WDrop High
6 mm²41 A32 A694.99 V (100.72%)0.0 V1146.4 V (166.15%)541687.5 WDrop High
10 mm²57 A44 A416.99 V (60.43%)273.0 V687.84 V (99.69%)325012.5 WDrop High
16 mm²76 A59 A260.62 V (37.77%)429.4 V429.9 V (62.3%)203132.8 WDrop High
25 mm²101 A78 A166.8 V (24.17%)523.2 V275.14 V (39.87%)130005.0 WDrop High
35 mm²125 A97 A119.14 V (17.27%)570.9 V196.53 V (28.48%)92860.7 WDrop High
50 mm²151 A118 A83.4 V (12.09%)606.6 V137.57 V (19.94%)65002.5 WDrop High
70 mm²192 A150 A59.57 V (8.63%)630.4 V98.26 V (14.24%)46430.4 WDrop High
95 mm²232 A181 A43.89 V (6.36%)646.1 V72.4 V (10.49%)34211.8 WDrop High
120 mm²269 A210 A34.75 V (5.04%)655.3 V57.32 V (8.31%)27084.4 WDrop High
150 mm²309 A241 A27.8 V (4.03%)662.2 V45.86 V (6.65%)21667.5 WDrop High
185 mm²353 A275 A22.54 V (3.27%)667.5 V37.18 V (5.39%)17568.2 WDrop High
240 mm²415 A324 A17.37 V (2.52%)672.6 V28.66 V (4.15%)13542.2 WDrop High
300 mm²477 A372 A13.9 V (2.01%)676.1 V22.93 V (3.32%)10833.8 W✓ OK (≤3%)
400 mm²570 A445 A10.42 V (1.51%)679.6 V17.2 V (2.49%)8125.3 W✓ OK (≤3%)

FAQ — 450 Amp Cable Size at 250 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 450A at 250 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 450A over 250m at 690V (voltage drop: 13.9V or 2.01%).

What is the power capacity of 450A at 690V?

At unity power factor, 450A at 690V supports 537.8 kW with a standard 450A circuit breaker.