475 Amp Cable Size at 80 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 475 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 4.7V (1.13%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.81V (1.4%)
Voltage at Load410.3 VLine Loss: 3862.7 W
Max Power & Breaker341.43 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A939.0 V (226.27%)0.0 V1548.92 V (373.23%)772540.0 WDrop High
2.5 mm²24 A18 A563.4 V (135.76%)0.0 V929.35 V (223.94%)463524.0 WDrop High
4 mm²32 A25 A352.13 V (84.85%)62.9 V580.84 V (139.96%)289702.5 WDrop High
6 mm²41 A32 A234.75 V (56.57%)180.2 V387.23 V (93.31%)193135.0 WDrop High
10 mm²57 A44 A140.85 V (33.94%)274.1 V232.34 V (55.98%)115881.0 WDrop High
16 mm²76 A59 A88.03 V (21.21%)327.0 V145.21 V (34.99%)72425.6 WDrop High
25 mm²101 A78 A56.34 V (13.58%)358.7 V92.93 V (22.39%)46352.4 WDrop High
35 mm²125 A97 A40.24 V (9.7%)374.8 V66.38 V (16.0%)33108.9 WDrop High
50 mm²151 A118 A28.17 V (6.79%)386.8 V46.47 V (11.2%)23176.2 WDrop High
70 mm²192 A150 A20.12 V (4.85%)394.9 V33.19 V (8.0%)16554.4 WDrop High
95 mm²232 A181 A14.83 V (3.57%)400.2 V24.46 V (5.89%)12198.0 WDrop High
120 mm²269 A210 A11.74 V (2.83%)403.3 V19.36 V (4.67%)9656.8 WDrop High
150 mm²309 A241 A9.39 V (2.26%)405.6 V15.49 V (3.73%)7725.4 WDrop High
185 mm²353 A275 A7.61 V (1.83%)407.4 V12.56 V (3.03%)6263.8 WDrop High
240 mm²415 A324 A5.87 V (1.41%)409.1 V9.68 V (2.33%)4828.4 WDrop High
300 mm²477 A372 A4.7 V (1.13%)410.3 V7.74 V (1.87%)3862.7 W✓ OK (≤3%)
400 mm²570 A445 A3.52 V (0.85%)411.5 V5.81 V (1.4%)2897.0 W✓ OK (≤3%)

FAQ — 475 Amp Cable Size at 80 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 475A at 80 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 475A over 80m at 415V (voltage drop: 4.7V or 1.13%).

What is the power capacity of 475A at 415V?

At unity power factor, 475A at 415V supports 341.43 kW with a standard 500A circuit breaker.