475 Amp Cable Size at 80 Meters (415V Three-Phase (UK / Australia Industrial))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 475 A over 80 m (262.5 ft).
Copper Cable (≤3% Drop)300 mm²Drop: 4.7V (1.13%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.81V (1.4%)
Voltage at Load410.3 VLine Loss: 3862.7 W
Max Power & Breaker341.43 kW500A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 80m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 939.0 V (226.27%) | 0.0 V | 1548.92 V (373.23%) | 772540.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 563.4 V (135.76%) | 0.0 V | 929.35 V (223.94%) | 463524.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 352.13 V (84.85%) | 62.9 V | 580.84 V (139.96%) | 289702.5 W | Drop High |
| 6 mm² | 41 A | 32 A | 234.75 V (56.57%) | 180.2 V | 387.23 V (93.31%) | 193135.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 140.85 V (33.94%) | 274.1 V | 232.34 V (55.98%) | 115881.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 88.03 V (21.21%) | 327.0 V | 145.21 V (34.99%) | 72425.6 W | Drop High |
| 25 mm² | 101 A | 78 A | 56.34 V (13.58%) | 358.7 V | 92.93 V (22.39%) | 46352.4 W | Drop High |
| 35 mm² | 125 A | 97 A | 40.24 V (9.7%) | 374.8 V | 66.38 V (16.0%) | 33108.9 W | Drop High |
| 50 mm² | 151 A | 118 A | 28.17 V (6.79%) | 386.8 V | 46.47 V (11.2%) | 23176.2 W | Drop High |
| 70 mm² | 192 A | 150 A | 20.12 V (4.85%) | 394.9 V | 33.19 V (8.0%) | 16554.4 W | Drop High |
| 95 mm² | 232 A | 181 A | 14.83 V (3.57%) | 400.2 V | 24.46 V (5.89%) | 12198.0 W | Drop High |
| 120 mm² | 269 A | 210 A | 11.74 V (2.83%) | 403.3 V | 19.36 V (4.67%) | 9656.8 W | Drop High |
| 150 mm² | 309 A | 241 A | 9.39 V (2.26%) | 405.6 V | 15.49 V (3.73%) | 7725.4 W | Drop High |
| 185 mm² | 353 A | 275 A | 7.61 V (1.83%) | 407.4 V | 12.56 V (3.03%) | 6263.8 W | Drop High |
| 240 mm² | 415 A | 324 A | 5.87 V (1.41%) | 409.1 V | 9.68 V (2.33%) | 4828.4 W | Drop High |
| 300 mm² | 477 A | 372 A | 4.7 V (1.13%) | 410.3 V | 7.74 V (1.87%) | 3862.7 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 3.52 V (0.85%) | 411.5 V | 5.81 V (1.4%) | 2897.0 W | ✓ OK (≤3%) |
FAQ — 475 Amp Cable Size at 80 Meters (415V Three-Phase (UK / Australia Industrial))
What mm² cable size is required for 475A at 80 meters (415V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 475A over 80m at 415V (voltage drop: 4.7V or 1.13%).
What is the power capacity of 475A at 415V?
At unity power factor, 475A at 415V supports 341.43 kW with a standard 500A circuit breaker.
Related Lengths & Currents (415V)
475A · 5m (415V)475A · 10m (415V)475A · 15m (415V)475A · 20m (415V)475A · 25m (415V)475A · 30m (415V)475A · 35m (415V)475A · 40m (415V)475A · 45m (415V)475A · 50m (415V)475A · 60m (415V)475A · 70m (415V)10A · 80m (415V)16A · 80m (415V)20A · 80m (415V)25A · 80m (415V)32A · 80m (415V)40A · 80m (415V)50A · 80m (415V)63A · 80m (415V)80A · 80m (415V)100A · 80m (415V)125A · 80m (415V)160A · 80m (415V)200A · 80m (415V)