500 Amp Cable Size at 100 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 500 A over 100 m (328.1 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 4.63V (1.12%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 7.64V (1.84%)
Voltage at Load410.4 VLine Loss: 4012.5 W
Max Power & Breaker359.4 kW500A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 500A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1235.53 V (297.72%)0.0 V2038.05 V (491.1%)1070000.0 WDrop High
2.5 mm²24 A18 A741.32 V (178.63%)0.0 V1222.83 V (294.66%)642000.0 WDrop High
4 mm²32 A25 A463.32 V (111.64%)0.0 V764.27 V (184.16%)401250.0 WDrop High
6 mm²41 A32 A308.88 V (74.43%)106.1 V509.51 V (122.77%)267500.0 WDrop High
10 mm²57 A44 A185.33 V (44.66%)229.7 V305.71 V (73.66%)160500.0 WDrop High
16 mm²76 A59 A115.83 V (27.91%)299.2 V191.07 V (46.04%)100312.5 WDrop High
25 mm²101 A78 A74.13 V (17.86%)340.9 V122.28 V (29.47%)64200.0 WDrop High
35 mm²125 A97 A52.95 V (12.76%)362.0 V87.34 V (21.05%)45857.1 WDrop High
50 mm²151 A118 A37.07 V (8.93%)377.9 V61.14 V (14.73%)32100.0 WDrop High
70 mm²192 A150 A26.48 V (6.38%)388.5 V43.67 V (10.52%)22928.6 WDrop High
95 mm²232 A181 A19.51 V (4.7%)395.5 V32.18 V (7.75%)16894.7 WDrop High
120 mm²269 A210 A15.44 V (3.72%)399.6 V25.48 V (6.14%)13375.0 WDrop High
150 mm²309 A241 A12.36 V (2.98%)402.6 V20.38 V (4.91%)10700.0 WDrop High
185 mm²353 A275 A10.02 V (2.41%)405.0 V16.52 V (3.98%)8675.7 WDrop High
240 mm²415 A324 A7.72 V (1.86%)407.3 V12.74 V (3.07%)6687.5 WDrop High
300 mm²477 A372 A6.18 V (1.49%)408.8 V10.19 V (2.46%)5350.0 WDrop High
400 mm²570 A445 A4.63 V (1.12%)410.4 V7.64 V (1.84%)4012.5 W✓ OK (≤3%)

FAQ — 500 Amp Cable Size at 100 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 500A at 100 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 500A over 100m at 415V (voltage drop: 4.63V or 1.12%).

What is the power capacity of 500A at 415V?

At unity power factor, 500A at 415V supports 359.4 kW with a standard 500A circuit breaker.