⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

550 Amp Cable Size at 10 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 10 m (32.8 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 0.51V (0.12%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.84V (0.2%)
Voltage at Load414.5 VLine Loss: 485.5 W
Max Power & Breaker395.34 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A135.91 V (32.75%)279.1 V224.19 V (54.02%)129470.0 WDrop High
2.5 mm²24 A18 A81.54 V (19.65%)333.5 V134.51 V (32.41%)77682.0 WDrop High
4 mm²32 A25 A50.97 V (12.28%)364.0 V84.07 V (20.26%)48551.2 WDrop High
6 mm²41 A32 A33.98 V (8.19%)381.0 V56.05 V (13.51%)32367.5 WDrop High
10 mm²57 A44 A20.39 V (4.91%)394.6 V33.63 V (8.1%)19420.5 WDrop High
16 mm²76 A59 A12.74 V (3.07%)402.3 V21.02 V (5.06%)12137.8 WDrop High
25 mm²101 A78 A8.15 V (1.96%)406.8 V13.45 V (3.24%)7768.2 WDrop High
35 mm²125 A97 A5.82 V (1.4%)409.2 V9.61 V (2.32%)5548.7 WDrop High
50 mm²151 A118 A4.08 V (0.98%)410.9 V6.73 V (1.62%)3884.1 WDrop High
70 mm²192 A150 A2.91 V (0.7%)412.1 V4.8 V (1.16%)2774.4 WDrop High
95 mm²232 A181 A2.15 V (0.52%)412.9 V3.54 V (0.85%)2044.3 WDrop High
120 mm²269 A210 A1.7 V (0.41%)413.3 V2.8 V (0.68%)1618.4 WDrop High
150 mm²309 A241 A1.36 V (0.33%)413.6 V2.24 V (0.54%)1294.7 WDrop High
185 mm²353 A275 A1.1 V (0.27%)413.9 V1.82 V (0.44%)1049.8 WDrop High
240 mm²415 A324 A0.85 V (0.2%)414.2 V1.4 V (0.34%)809.2 WDrop High
300 mm²477 A372 A0.68 V (0.16%)414.3 V1.12 V (0.27%)647.3 WDrop High
400 mm²570 A445 A0.51 V (0.12%)414.5 V0.84 V (0.2%)485.5 W✓ OK (≤3%)

FAQ — 550 Amp Cable Size at 10 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 550A at 10 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 550A over 10m at 415V (voltage drop: 0.51V or 0.12%).

What is the power capacity of 550A at 415V?

At unity power factor, 550A at 415V supports 395.34 kW with a standard 600A circuit breaker.