⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

550 Amp Cable Size at 40 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 40 m (131.2 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 2.04V (0.49%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 3.36V (0.81%)
Voltage at Load413.0 VLine Loss: 1942.0 W
Max Power & Breaker395.34 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 40m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A543.63 V (131.0%)0.0 V896.74 V (216.08%)517880.0 WDrop High
2.5 mm²24 A18 A326.18 V (78.6%)88.8 V538.04 V (129.65%)310728.0 WDrop High
4 mm²32 A25 A203.86 V (49.12%)211.1 V336.28 V (81.03%)194205.0 WDrop High
6 mm²41 A32 A135.91 V (32.75%)279.1 V224.19 V (54.02%)129470.0 WDrop High
10 mm²57 A44 A81.54 V (19.65%)333.5 V134.51 V (32.41%)77682.0 WDrop High
16 mm²76 A59 A50.97 V (12.28%)364.0 V84.07 V (20.26%)48551.2 WDrop High
25 mm²101 A78 A32.62 V (7.86%)382.4 V53.8 V (12.96%)31072.8 WDrop High
35 mm²125 A97 A23.3 V (5.61%)391.7 V38.43 V (9.26%)22194.9 WDrop High
50 mm²151 A118 A16.31 V (3.93%)398.7 V26.9 V (6.48%)15536.4 WDrop High
70 mm²192 A150 A11.65 V (2.81%)403.4 V19.22 V (4.63%)11097.4 WDrop High
95 mm²232 A181 A8.58 V (2.07%)406.4 V14.16 V (3.41%)8177.1 WDrop High
120 mm²269 A210 A6.8 V (1.64%)408.2 V11.21 V (2.7%)6473.5 WDrop High
150 mm²309 A241 A5.44 V (1.31%)409.6 V8.97 V (2.16%)5178.8 WDrop High
185 mm²353 A275 A4.41 V (1.06%)410.6 V7.27 V (1.75%)4199.0 WDrop High
240 mm²415 A324 A3.4 V (0.82%)411.6 V5.6 V (1.35%)3236.8 WDrop High
300 mm²477 A372 A2.72 V (0.65%)412.3 V4.48 V (1.08%)2589.4 WDrop High
400 mm²570 A445 A2.04 V (0.49%)413.0 V3.36 V (0.81%)1942.0 W✓ OK (≤3%)

FAQ — 550 Amp Cable Size at 40 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 550A at 40 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 550A over 40m at 415V (voltage drop: 2.04V or 0.49%).

What is the power capacity of 550A at 415V?

At unity power factor, 550A at 415V supports 395.34 kW with a standard 600A circuit breaker.