550 Amp Cable Size at 5 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 0.25V (0.06%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.42V (0.1%)
Voltage at Load414.7 VLine Loss: 242.8 W
Max Power & Breaker395.34 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A67.95 V (16.37%)347.0 V112.09 V (27.01%)64735.0 WDrop High
2.5 mm²24 A18 A40.77 V (9.82%)374.2 V67.26 V (16.21%)38841.0 WDrop High
4 mm²32 A25 A25.48 V (6.14%)389.5 V42.03 V (10.13%)24275.6 WDrop High
6 mm²41 A32 A16.99 V (4.09%)398.0 V28.02 V (6.75%)16183.8 WDrop High
10 mm²57 A44 A10.19 V (2.46%)404.8 V16.81 V (4.05%)9710.2 WDrop High
16 mm²76 A59 A6.37 V (1.54%)408.6 V10.51 V (2.53%)6068.9 WDrop High
25 mm²101 A78 A4.08 V (0.98%)410.9 V6.73 V (1.62%)3884.1 WDrop High
35 mm²125 A97 A2.91 V (0.7%)412.1 V4.8 V (1.16%)2774.4 WDrop High
50 mm²151 A118 A2.04 V (0.49%)413.0 V3.36 V (0.81%)1942.0 WDrop High
70 mm²192 A150 A1.46 V (0.35%)413.5 V2.4 V (0.58%)1387.2 WDrop High
95 mm²232 A181 A1.07 V (0.26%)413.9 V1.77 V (0.43%)1022.1 WDrop High
120 mm²269 A210 A0.85 V (0.2%)414.2 V1.4 V (0.34%)809.2 WDrop High
150 mm²309 A241 A0.68 V (0.16%)414.3 V1.12 V (0.27%)647.3 WDrop High
185 mm²353 A275 A0.55 V (0.13%)414.4 V0.91 V (0.22%)524.9 WDrop High
240 mm²415 A324 A0.42 V (0.1%)414.6 V0.7 V (0.17%)404.6 WDrop High
300 mm²477 A372 A0.34 V (0.08%)414.7 V0.56 V (0.14%)323.7 WDrop High
400 mm²570 A445 A0.25 V (0.06%)414.7 V0.42 V (0.1%)242.8 W✓ OK (≤3%)

FAQ — 550 Amp Cable Size at 5 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 550A at 5 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 550A over 5m at 415V (voltage drop: 0.25V or 0.06%).

What is the power capacity of 550A at 415V?

At unity power factor, 550A at 415V supports 395.34 kW with a standard 600A circuit breaker.