550 Amp Cable Size at 45 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 45 m (147.6 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 2.29V (0.55%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 3.78V (0.91%)
Voltage at Load412.7 VLine Loss: 2184.8 W
Max Power & Breaker395.34 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A611.59 V (147.37%)0.0 V1008.83 V (243.09%)582615.0 WDrop High
2.5 mm²24 A18 A366.95 V (88.42%)48.0 V605.3 V (145.86%)349569.0 WDrop High
4 mm²32 A25 A229.35 V (55.26%)185.7 V378.31 V (91.16%)218480.6 WDrop High
6 mm²41 A32 A152.9 V (36.84%)262.1 V252.21 V (60.77%)145653.8 WDrop High
10 mm²57 A44 A91.74 V (22.11%)323.3 V151.32 V (36.46%)87392.2 WDrop High
16 mm²76 A59 A57.34 V (13.82%)357.7 V94.58 V (22.79%)54620.2 WDrop High
25 mm²101 A78 A36.7 V (8.84%)378.3 V60.53 V (14.59%)34956.9 WDrop High
35 mm²125 A97 A26.21 V (6.32%)388.8 V43.24 V (10.42%)24969.2 WDrop High
50 mm²151 A118 A18.35 V (4.42%)396.7 V30.26 V (7.29%)17478.5 WDrop High
70 mm²192 A150 A13.11 V (3.16%)401.9 V21.62 V (5.21%)12484.6 WDrop High
95 mm²232 A181 A9.66 V (2.33%)405.3 V15.93 V (3.84%)9199.2 WDrop High
120 mm²269 A210 A7.64 V (1.84%)407.4 V12.61 V (3.04%)7282.7 WDrop High
150 mm²309 A241 A6.12 V (1.47%)408.9 V10.09 V (2.43%)5826.1 WDrop High
185 mm²353 A275 A4.96 V (1.19%)410.0 V8.18 V (1.97%)4723.9 WDrop High
240 mm²415 A324 A3.82 V (0.92%)411.2 V6.31 V (1.52%)3641.3 WDrop High
300 mm²477 A372 A3.06 V (0.74%)411.9 V5.04 V (1.22%)2913.1 WDrop High
400 mm²570 A445 A2.29 V (0.55%)412.7 V3.78 V (0.91%)2184.8 W✓ OK (≤3%)

FAQ — 550 Amp Cable Size at 45 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 550A at 45 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 550A over 45m at 415V (voltage drop: 2.29V or 0.55%).

What is the power capacity of 550A at 415V?

At unity power factor, 550A at 415V supports 395.34 kW with a standard 600A circuit breaker.