550 Amp Cable Size at 50 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 50 m (164.0 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 2.55V (0.61%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 4.2V (1.01%)
Voltage at Load412.5 VLine Loss: 2427.6 W
Max Power & Breaker395.34 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A679.54 V (163.74%)0.0 V1120.93 V (270.1%)647350.0 WDrop High
2.5 mm²24 A18 A407.72 V (98.25%)7.3 V672.56 V (162.06%)388410.0 WDrop High
4 mm²32 A25 A254.83 V (61.4%)160.2 V420.35 V (101.29%)242756.2 WDrop High
6 mm²41 A32 A169.89 V (40.94%)245.1 V280.23 V (67.53%)161837.5 WDrop High
10 mm²57 A44 A101.93 V (24.56%)313.1 V168.14 V (40.52%)97102.5 WDrop High
16 mm²76 A59 A63.71 V (15.35%)351.3 V105.09 V (25.32%)60689.1 WDrop High
25 mm²101 A78 A40.77 V (9.82%)374.2 V67.26 V (16.21%)38841.0 WDrop High
35 mm²125 A97 A29.12 V (7.02%)385.9 V48.04 V (11.58%)27743.6 WDrop High
50 mm²151 A118 A20.39 V (4.91%)394.6 V33.63 V (8.1%)19420.5 WDrop High
70 mm²192 A150 A14.56 V (3.51%)400.4 V24.02 V (5.79%)13871.8 WDrop High
95 mm²232 A181 A10.73 V (2.59%)404.3 V17.7 V (4.26%)10221.3 WDrop High
120 mm²269 A210 A8.49 V (2.05%)406.5 V14.01 V (3.38%)8091.9 WDrop High
150 mm²309 A241 A6.8 V (1.64%)408.2 V11.21 V (2.7%)6473.5 WDrop High
185 mm²353 A275 A5.51 V (1.33%)409.5 V9.09 V (2.19%)5248.8 WDrop High
240 mm²415 A324 A4.25 V (1.02%)410.8 V7.01 V (1.69%)4045.9 WDrop High
300 mm²477 A372 A3.4 V (0.82%)411.6 V5.6 V (1.35%)3236.7 WDrop High
400 mm²570 A445 A2.55 V (0.61%)412.5 V4.2 V (1.01%)2427.6 W✓ OK (≤3%)

FAQ — 550 Amp Cable Size at 50 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 550A at 50 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 550A over 50m at 415V (voltage drop: 2.55V or 0.61%).

What is the power capacity of 550A at 415V?

At unity power factor, 550A at 415V supports 395.34 kW with a standard 600A circuit breaker.