550 Amp Cable Size at 15 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 15 m (49.2 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 0.76V (0.18%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.26V (0.3%)
Voltage at Load414.2 VLine Loss: 728.3 W
Max Power & Breaker395.34 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A203.86 V (49.12%)211.1 V336.28 V (81.03%)194205.0 WDrop High
2.5 mm²24 A18 A122.32 V (29.47%)292.7 V201.77 V (48.62%)116523.0 WDrop High
4 mm²32 A25 A76.45 V (18.42%)338.6 V126.1 V (30.39%)72826.9 WDrop High
6 mm²41 A32 A50.97 V (12.28%)364.0 V84.07 V (20.26%)48551.2 WDrop High
10 mm²57 A44 A30.58 V (7.37%)384.4 V50.44 V (12.15%)29130.8 WDrop High
16 mm²76 A59 A19.11 V (4.61%)395.9 V31.53 V (7.6%)18206.7 WDrop High
25 mm²101 A78 A12.23 V (2.95%)402.8 V20.18 V (4.86%)11652.3 WDrop High
35 mm²125 A97 A8.74 V (2.11%)406.3 V14.41 V (3.47%)8323.1 WDrop High
50 mm²151 A118 A6.12 V (1.47%)408.9 V10.09 V (2.43%)5826.2 WDrop High
70 mm²192 A150 A4.37 V (1.05%)410.6 V7.21 V (1.74%)4161.5 WDrop High
95 mm²232 A181 A3.22 V (0.78%)411.8 V5.31 V (1.28%)3066.4 WDrop High
120 mm²269 A210 A2.55 V (0.61%)412.5 V4.2 V (1.01%)2427.6 WDrop High
150 mm²309 A241 A2.04 V (0.49%)413.0 V3.36 V (0.81%)1942.0 WDrop High
185 mm²353 A275 A1.65 V (0.4%)413.3 V2.73 V (0.66%)1574.6 WDrop High
240 mm²415 A324 A1.27 V (0.31%)413.7 V2.1 V (0.51%)1213.8 WDrop High
300 mm²477 A372 A1.02 V (0.25%)414.0 V1.68 V (0.41%)971.0 WDrop High
400 mm²570 A445 A0.76 V (0.18%)414.2 V1.26 V (0.3%)728.3 W✓ OK (≤3%)

FAQ — 550 Amp Cable Size at 15 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 550A at 15 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 550A over 15m at 415V (voltage drop: 0.76V or 0.18%).

What is the power capacity of 550A at 415V?

At unity power factor, 550A at 415V supports 395.34 kW with a standard 600A circuit breaker.