⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

550 Amp Cable Size at 175 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 8.92V (1.29%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 14.71V (2.13%)
Voltage at Load681.1 VLine Loss: 8496.5 W
Max Power & Breaker657.31 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2378.39 V (344.69%)0.0 V3923.24 V (568.59%)2265725.0 WDrop High
2.5 mm²24 A18 A1427.04 V (206.82%)0.0 V2353.94 V (341.15%)1359435.0 WDrop High
4 mm²32 A25 A891.9 V (129.26%)0.0 V1471.21 V (213.22%)849646.9 WDrop High
6 mm²41 A32 A594.6 V (86.17%)95.4 V980.81 V (142.15%)566431.2 WDrop High
10 mm²57 A44 A356.76 V (51.7%)333.2 V588.49 V (85.29%)339858.7 WDrop High
16 mm²76 A59 A222.97 V (32.32%)467.0 V367.8 V (53.3%)212411.7 WDrop High
25 mm²101 A78 A142.7 V (20.68%)547.3 V235.39 V (34.12%)135943.5 WDrop High
35 mm²125 A97 A101.93 V (14.77%)588.1 V168.14 V (24.37%)97102.5 WDrop High
50 mm²151 A118 A71.35 V (10.34%)618.6 V117.7 V (17.06%)67971.8 WDrop High
70 mm²192 A150 A50.97 V (7.39%)639.0 V84.07 V (12.18%)48551.2 WDrop High
95 mm²232 A181 A37.55 V (5.44%)652.4 V61.95 V (8.98%)35774.6 WDrop High
120 mm²269 A210 A29.73 V (4.31%)660.3 V49.04 V (7.11%)28321.6 WDrop High
150 mm²309 A241 A23.78 V (3.45%)666.2 V39.23 V (5.69%)22657.2 WDrop High
185 mm²353 A275 A19.28 V (2.79%)670.7 V31.81 V (4.61%)18370.7 WDrop High
240 mm²415 A324 A14.86 V (2.15%)675.1 V24.52 V (3.55%)14160.8 WDrop High
300 mm²477 A372 A11.89 V (1.72%)678.1 V19.62 V (2.84%)11328.6 WDrop High
400 mm²570 A445 A8.92 V (1.29%)681.1 V14.71 V (2.13%)8496.5 W✓ OK (≤3%)

FAQ — 550 Amp Cable Size at 175 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 550A at 175 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 550A over 175m at 690V (voltage drop: 8.92V or 1.29%).

What is the power capacity of 550A at 690V?

At unity power factor, 550A at 690V supports 657.31 kW with a standard 600A circuit breaker.