550 Amp Cable Size at 350 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 17.84V (2.59%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 29.42V (4.26%)
Voltage at Load672.2 VLine Loss: 16992.9 W
Max Power & Breaker657.31 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4756.79 V (689.39%)0.0 V7846.48 V (1137.17%)4531450.0 WDrop High
2.5 mm²24 A18 A2854.07 V (413.63%)0.0 V4707.89 V (682.3%)2718870.0 WDrop High
4 mm²32 A25 A1783.8 V (258.52%)0.0 V2942.43 V (426.44%)1699293.7 WDrop High
6 mm²41 A32 A1189.2 V (172.35%)0.0 V1961.62 V (284.29%)1132862.5 WDrop High
10 mm²57 A44 A713.52 V (103.41%)0.0 V1176.97 V (170.58%)679717.5 WDrop High
16 mm²76 A59 A445.95 V (64.63%)244.1 V735.61 V (106.61%)424823.4 WDrop High
25 mm²101 A78 A285.41 V (41.36%)404.6 V470.79 V (68.23%)271887.0 WDrop High
35 mm²125 A97 A203.86 V (29.55%)486.1 V336.28 V (48.74%)194205.0 WDrop High
50 mm²151 A118 A142.7 V (20.68%)547.3 V235.39 V (34.12%)135943.5 WDrop High
70 mm²192 A150 A101.93 V (14.77%)588.1 V168.14 V (24.37%)97102.5 WDrop High
95 mm²232 A181 A75.11 V (10.89%)614.9 V123.89 V (17.96%)71549.2 WDrop High
120 mm²269 A210 A59.46 V (8.62%)630.5 V98.08 V (14.21%)56643.1 WDrop High
150 mm²309 A241 A47.57 V (6.89%)642.4 V78.46 V (11.37%)45314.5 WDrop High
185 mm²353 A275 A38.57 V (5.59%)651.4 V63.62 V (9.22%)36741.5 WDrop High
240 mm²415 A324 A29.73 V (4.31%)660.3 V49.04 V (7.11%)28321.6 WDrop High
300 mm²477 A372 A23.78 V (3.45%)666.2 V39.23 V (5.69%)22657.2 WDrop High
400 mm²570 A445 A17.84 V (2.59%)672.2 V29.42 V (4.26%)16992.9 W✓ OK (≤3%)

FAQ — 550 Amp Cable Size at 350 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 550A at 350 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 550A over 350m at 690V (voltage drop: 17.84V or 2.59%).

What is the power capacity of 550A at 690V?

At unity power factor, 550A at 690V supports 657.31 kW with a standard 600A circuit breaker.