550 Amp Cable Size at 400 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 400 m (1312.3 ft).

Copper Cable (≤3% Drop)17× 400 mm²Drop: 1.38V (2.88%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 38.83V (80.9%)
Voltage at Load46.6 VLine Loss: 761.6 W
Max Power & Breaker26.4 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A6277.33 V (13077.78%)0.0 V10354.67 V (21572.22%)3452533.3 WDrop High
2.5 mm²24 A18 A3766.4 V (7846.67%)0.0 V6212.8 V (12943.33%)2071520.0 WDrop High
4 mm²32 A25 A2354.0 V (4904.17%)0.0 V3883.0 V (8089.58%)1294700.0 WDrop High
6 mm²41 A32 A1569.33 V (3269.44%)0.0 V2588.67 V (5393.06%)863133.3 WDrop High
10 mm²57 A44 A941.6 V (1961.67%)0.0 V1553.2 V (3235.83%)517880.0 WDrop High
16 mm²76 A59 A588.5 V (1226.04%)0.0 V970.75 V (2022.4%)323675.0 WDrop High
25 mm²101 A78 A376.64 V (784.67%)0.0 V621.28 V (1294.33%)207152.0 WDrop High
35 mm²125 A97 A269.03 V (560.48%)0.0 V443.77 V (924.52%)147965.7 WDrop High
50 mm²151 A118 A188.32 V (392.33%)0.0 V310.64 V (647.17%)103576.0 WDrop High
70 mm²192 A150 A134.51 V (280.24%)0.0 V221.89 V (462.26%)73982.9 WDrop High
95 mm²232 A181 A99.12 V (206.49%)0.0 V163.49 V (340.61%)54513.7 WDrop High
120 mm²269 A210 A78.47 V (163.47%)0.0 V129.43 V (269.65%)43156.7 WDrop High
150 mm²309 A241 A62.77 V (130.78%)0.0 V103.55 V (215.72%)34525.3 WDrop High
185 mm²353 A275 A50.9 V (106.04%)0.0 V83.96 V (174.91%)27993.5 WDrop High
240 mm²415 A324 A39.23 V (81.74%)8.8 V64.72 V (134.83%)21578.3 WDrop High
300 mm²477 A372 A31.39 V (65.39%)16.6 V51.77 V (107.86%)17262.7 WDrop High
400 mm²570 A445 A23.54 V (49.04%)24.5 V38.83 V (80.9%)12947.0 WDrop High

FAQ — 550 Amp Cable Size at 400 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 550A at 400 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 17× 400 mm² copper cable for 550A over 400m at 48V (voltage drop: 1.38V or 2.88%).

What is the power capacity of 550A at 48V?

At unity power factor, 550A at 48V supports 26.4 kW with a standard 600A circuit breaker.