550 Amp Cable Size at 80 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)4× 400 mm²Drop: 1.18V (2.45%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 7.77V (16.18%)
Voltage at Load46.8 VLine Loss: 647.4 W
Max Power & Breaker26.4 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1255.47 V (2615.56%)0.0 V2070.93 V (4314.44%)690506.7 WDrop High
2.5 mm²24 A18 A753.28 V (1569.33%)0.0 V1242.56 V (2588.67%)414304.0 WDrop High
4 mm²32 A25 A470.8 V (980.83%)0.0 V776.6 V (1617.92%)258940.0 WDrop High
6 mm²41 A32 A313.87 V (653.89%)0.0 V517.73 V (1078.61%)172626.7 WDrop High
10 mm²57 A44 A188.32 V (392.33%)0.0 V310.64 V (647.17%)103576.0 WDrop High
16 mm²76 A59 A117.7 V (245.21%)0.0 V194.15 V (404.48%)64735.0 WDrop High
25 mm²101 A78 A75.33 V (156.93%)0.0 V124.26 V (258.87%)41430.4 WDrop High
35 mm²125 A97 A53.81 V (112.1%)0.0 V88.75 V (184.9%)29593.1 WDrop High
50 mm²151 A118 A37.66 V (78.47%)10.3 V62.13 V (129.43%)20715.2 WDrop High
70 mm²192 A150 A26.9 V (56.05%)21.1 V44.38 V (92.45%)14796.6 WDrop High
95 mm²232 A181 A19.82 V (41.3%)28.2 V32.7 V (68.12%)10902.7 WDrop High
120 mm²269 A210 A15.69 V (32.69%)32.3 V25.89 V (53.93%)8631.3 WDrop High
150 mm²309 A241 A12.55 V (26.16%)35.4 V20.71 V (43.14%)6905.1 WDrop High
185 mm²353 A275 A10.18 V (21.21%)37.8 V16.79 V (34.98%)5598.7 WDrop High
240 mm²415 A324 A7.85 V (16.35%)40.2 V12.94 V (26.97%)4315.7 WDrop High
300 mm²477 A372 A6.28 V (13.08%)41.7 V10.35 V (21.57%)3452.5 WDrop High
400 mm²570 A445 A4.71 V (9.81%)43.3 V7.77 V (16.18%)2589.4 WDrop High

FAQ — 550 Amp Cable Size at 80 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 550A at 80 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4× 400 mm² copper cable for 550A over 80m at 48V (voltage drop: 1.18V or 2.45%).

What is the power capacity of 550A at 48V?

At unity power factor, 550A at 48V supports 26.4 kW with a standard 600A circuit breaker.