⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

600 Amp Cable Size at 350 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 600 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 9.73V (2.35%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 32.1V (7.73%)
Voltage at Load405.3 VLine Loss: 10111.5 W
Max Power & Breaker431.28 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 600A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A5189.22 V (1250.42%)0.0 V8559.8 V (2062.6%)5392800.0 WDrop High
2.5 mm²24 A18 A3113.53 V (750.25%)0.0 V5135.88 V (1237.56%)3235680.0 WDrop High
4 mm²32 A25 A1945.96 V (468.91%)0.0 V3209.92 V (773.48%)2022300.0 WDrop High
6 mm²41 A32 A1297.31 V (312.6%)0.0 V2139.95 V (515.65%)1348200.0 WDrop High
10 mm²57 A44 A778.38 V (187.56%)0.0 V1283.97 V (309.39%)808920.0 WDrop High
16 mm²76 A59 A486.49 V (117.23%)0.0 V802.48 V (193.37%)505575.0 WDrop High
25 mm²101 A78 A311.35 V (75.02%)103.6 V513.59 V (123.76%)323568.0 WDrop High
35 mm²125 A97 A222.4 V (53.59%)192.6 V366.85 V (88.4%)231120.0 WDrop High
50 mm²151 A118 A155.68 V (37.51%)259.3 V256.79 V (61.88%)161784.0 WDrop High
70 mm²192 A150 A111.2 V (26.79%)303.8 V183.42 V (44.2%)115560.0 WDrop High
95 mm²232 A181 A81.94 V (19.74%)333.1 V135.15 V (32.57%)85149.5 WDrop High
120 mm²269 A210 A64.87 V (15.63%)350.1 V107.0 V (25.78%)67410.0 WDrop High
150 mm²309 A241 A51.89 V (12.5%)363.1 V85.6 V (20.63%)53928.0 WDrop High
185 mm²353 A275 A42.07 V (10.14%)372.9 V69.4 V (16.72%)43725.4 WDrop High
240 mm²415 A324 A32.43 V (7.82%)382.6 V53.5 V (12.89%)33705.0 WDrop High
300 mm²477 A372 A25.95 V (6.25%)389.1 V42.8 V (10.31%)26964.0 WDrop High
400 mm²570 A445 A19.46 V (4.69%)395.5 V32.1 V (7.73%)20223.0 WDrop High

FAQ — 600 Amp Cable Size at 350 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 600A at 350 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 600A over 350m at 415V (voltage drop: 9.73V or 2.35%).

What is the power capacity of 600A at 415V?

At unity power factor, 600A at 415V supports 431.28 kW with a standard 600A circuit breaker.