700 Amp Cable Size at 120 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 700 A over 120 m (393.7 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 3.89V (0.56%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 12.84V (1.86%)
Voltage at Load686.1 VLine Loss: 4718.7 W
Max Power & Breaker836.58 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2075.69 V (300.82%)0.0 V3423.92 V (496.22%)2516640.0 WDrop High
2.5 mm²24 A18 A1245.41 V (180.49%)0.0 V2054.35 V (297.73%)1509984.0 WDrop High
4 mm²32 A25 A778.38 V (112.81%)0.0 V1283.97 V (186.08%)943740.0 WDrop High
6 mm²41 A32 A518.92 V (75.21%)171.1 V855.98 V (124.06%)629160.0 WDrop High
10 mm²57 A44 A311.35 V (45.12%)378.6 V513.59 V (74.43%)377496.0 WDrop High
16 mm²76 A59 A194.6 V (28.2%)495.4 V320.99 V (46.52%)235935.0 WDrop High
25 mm²101 A78 A124.54 V (18.05%)565.5 V205.44 V (29.77%)150998.4 WDrop High
35 mm²125 A97 A88.96 V (12.89%)601.0 V146.74 V (21.27%)107856.0 WDrop High
50 mm²151 A118 A62.27 V (9.02%)627.7 V102.72 V (14.89%)75499.2 WDrop High
70 mm²192 A150 A44.48 V (6.45%)645.5 V73.37 V (10.63%)53928.0 WDrop High
95 mm²232 A181 A32.77 V (4.75%)657.2 V54.06 V (7.84%)39736.4 WDrop High
120 mm²269 A210 A25.95 V (3.76%)664.1 V42.8 V (6.2%)31458.0 WDrop High
150 mm²309 A241 A20.76 V (3.01%)669.2 V34.24 V (4.96%)25166.4 WDrop High
185 mm²353 A275 A16.83 V (2.44%)673.2 V27.76 V (4.02%)20405.2 WDrop High
240 mm²415 A324 A12.97 V (1.88%)677.0 V21.4 V (3.1%)15729.0 WDrop High
300 mm²477 A372 A10.38 V (1.5%)679.6 V17.12 V (2.48%)12583.2 WDrop High
400 mm²570 A445 A7.78 V (1.13%)682.2 V12.84 V (1.86%)9437.4 WDrop High

FAQ — 700 Amp Cable Size at 120 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 700A at 120 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 700A over 120m at 690V (voltage drop: 3.89V or 0.56%).

What is the power capacity of 700A at 690V?

At unity power factor, 700A at 690V supports 836.58 kW with a standard 700A circuit breaker.