700 Amp Cable Size at 200 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 700 A over 200 m (656.2 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 6.49V (1.56%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 21.4V (5.16%)
Voltage at Load408.5 VLine Loss: 7864.5 W
Max Power & Breaker503.16 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 200m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3459.48 V (833.61%)0.0 V5706.53 V (1375.07%)4194400.0 WDrop High
2.5 mm²24 A18 A2075.69 V (500.17%)0.0 V3423.92 V (825.04%)2516640.0 WDrop High
4 mm²32 A25 A1297.31 V (312.6%)0.0 V2139.95 V (515.65%)1572900.0 WDrop High
6 mm²41 A32 A864.87 V (208.4%)0.0 V1426.63 V (343.77%)1048600.0 WDrop High
10 mm²57 A44 A518.92 V (125.04%)0.0 V855.98 V (206.26%)629160.0 WDrop High
16 mm²76 A59 A324.33 V (78.15%)90.7 V534.99 V (128.91%)393225.0 WDrop High
25 mm²101 A78 A207.57 V (50.02%)207.4 V342.39 V (82.5%)251664.0 WDrop High
35 mm²125 A97 A148.26 V (35.73%)266.7 V244.57 V (58.93%)179760.0 WDrop High
50 mm²151 A118 A103.78 V (25.01%)311.2 V171.2 V (41.25%)125832.0 WDrop High
70 mm²192 A150 A74.13 V (17.86%)340.9 V122.28 V (29.47%)89880.0 WDrop High
95 mm²232 A181 A54.62 V (13.16%)360.4 V90.1 V (21.71%)66227.4 WDrop High
120 mm²269 A210 A43.24 V (10.42%)371.8 V71.33 V (17.19%)52430.0 WDrop High
150 mm²309 A241 A34.59 V (8.34%)380.4 V57.07 V (13.75%)41944.0 WDrop High
185 mm²353 A275 A28.05 V (6.76%)387.0 V46.27 V (11.15%)34008.6 WDrop High
240 mm²415 A324 A21.62 V (5.21%)393.4 V35.67 V (8.59%)26215.0 WDrop High
300 mm²477 A372 A17.3 V (4.17%)397.7 V28.53 V (6.88%)20972.0 WDrop High
400 mm²570 A445 A12.97 V (3.13%)402.0 V21.4 V (5.16%)15729.0 WDrop High

FAQ — 700 Amp Cable Size at 200 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 700A at 200 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 700A over 200m at 415V (voltage drop: 6.49V or 1.56%).

What is the power capacity of 700A at 415V?

At unity power factor, 700A at 415V supports 503.16 kW with a standard 700A circuit breaker.