800 Amp Cable Size at 100 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 800 A over 100 m (328.1 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 3.71V (0.9%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 12.23V (2.95%)
Voltage at Load411.3 VLine Loss: 5136.0 W
Max Power & Breaker575.04 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 800A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1976.85 V (476.35%)0.0 V3260.87 V (785.75%)2739200.0 WDrop High
2.5 mm²24 A18 A1186.11 V (285.81%)0.0 V1956.52 V (471.45%)1643520.0 WDrop High
4 mm²32 A25 A741.32 V (178.63%)0.0 V1222.83 V (294.66%)1027200.0 WDrop High
6 mm²41 A32 A494.21 V (119.09%)0.0 V815.22 V (196.44%)684800.0 WDrop High
10 mm²57 A44 A296.53 V (71.45%)118.5 V489.13 V (117.86%)410880.0 WDrop High
16 mm²76 A59 A185.33 V (44.66%)229.7 V305.71 V (73.66%)256800.0 WDrop High
25 mm²101 A78 A118.61 V (28.58%)296.4 V195.65 V (47.15%)164352.0 WDrop High
35 mm²125 A97 A84.72 V (20.41%)330.3 V139.75 V (33.68%)117394.3 WDrop High
50 mm²151 A118 A59.31 V (14.29%)355.7 V97.83 V (23.57%)82176.0 WDrop High
70 mm²192 A150 A42.36 V (10.21%)372.6 V69.88 V (16.84%)58697.1 WDrop High
95 mm²232 A181 A31.21 V (7.52%)383.8 V51.49 V (12.41%)43250.5 WDrop High
120 mm²269 A210 A24.71 V (5.95%)390.3 V40.76 V (9.82%)34240.0 WDrop High
150 mm²309 A241 A19.77 V (4.76%)395.2 V32.61 V (7.86%)27392.0 WDrop High
185 mm²353 A275 A16.03 V (3.86%)399.0 V26.44 V (6.37%)22209.7 WDrop High
240 mm²415 A324 A12.36 V (2.98%)402.6 V20.38 V (4.91%)17120.0 WDrop High
300 mm²477 A372 A9.88 V (2.38%)405.1 V16.3 V (3.93%)13696.0 WDrop High
400 mm²570 A445 A7.41 V (1.79%)407.6 V12.23 V (2.95%)10272.0 WDrop High

FAQ — 800 Amp Cable Size at 100 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 800A at 100 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 800A over 100m at 415V (voltage drop: 3.71V or 0.9%).

What is the power capacity of 800A at 415V?

At unity power factor, 800A at 415V supports 575.04 kW with a standard 800A circuit breaker.