⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

800 Amp Cable Size at 175 Meters (400V Three-Phase (IEC European Grid))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 800 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 6.49V (1.62%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 21.4V (5.35%)
Voltage at Load393.5 VLine Loss: 8988.0 W
Max Power & Breaker554.26 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 800A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3459.48 V (864.87%)0.0 V5706.53 V (1426.63%)4793600.0 WDrop High
2.5 mm²24 A18 A2075.69 V (518.92%)0.0 V3423.92 V (855.98%)2876160.0 WDrop High
4 mm²32 A25 A1297.31 V (324.33%)0.0 V2139.95 V (534.99%)1797600.0 WDrop High
6 mm²41 A32 A864.87 V (216.22%)0.0 V1426.63 V (356.66%)1198400.0 WDrop High
10 mm²57 A44 A518.92 V (129.73%)0.0 V855.98 V (213.99%)719040.0 WDrop High
16 mm²76 A59 A324.33 V (81.08%)75.7 V534.99 V (133.75%)449400.0 WDrop High
25 mm²101 A78 A207.57 V (51.89%)192.4 V342.39 V (85.6%)287616.0 WDrop High
35 mm²125 A97 A148.26 V (37.07%)251.7 V244.57 V (61.14%)205440.0 WDrop High
50 mm²151 A118 A103.78 V (25.95%)296.2 V171.2 V (42.8%)143808.0 WDrop High
70 mm²192 A150 A74.13 V (18.53%)325.9 V122.28 V (30.57%)102720.0 WDrop High
95 mm²232 A181 A54.62 V (13.66%)345.4 V90.1 V (22.53%)75688.4 WDrop High
120 mm²269 A210 A43.24 V (10.81%)356.8 V71.33 V (17.83%)59920.0 WDrop High
150 mm²309 A241 A34.59 V (8.65%)365.4 V57.07 V (14.27%)47936.0 WDrop High
185 mm²353 A275 A28.05 V (7.01%)372.0 V46.27 V (11.57%)38867.0 WDrop High
240 mm²415 A324 A21.62 V (5.41%)378.4 V35.67 V (8.92%)29960.0 WDrop High
300 mm²477 A372 A17.3 V (4.32%)382.7 V28.53 V (7.13%)23968.0 WDrop High
400 mm²570 A445 A12.97 V (3.24%)387.0 V21.4 V (5.35%)17976.0 WDrop High

FAQ — 800 Amp Cable Size at 175 Meters (400V Three-Phase (IEC European Grid))

What mm² cable size is required for 800A at 175 meters (400V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 800A over 175m at 400V (voltage drop: 6.49V or 1.62%).

What is the power capacity of 800A at 400V?

At unity power factor, 800A at 400V supports 554.26 kW with a standard 800A circuit breaker.