⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

800 Amp Cable Size at 175 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 800 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 6.49V (1.56%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 21.4V (5.16%)
Voltage at Load408.5 VLine Loss: 8988.0 W
Max Power & Breaker575.04 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 800A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3459.48 V (833.61%)0.0 V5706.53 V (1375.07%)4793600.0 WDrop High
2.5 mm²24 A18 A2075.69 V (500.17%)0.0 V3423.92 V (825.04%)2876160.0 WDrop High
4 mm²32 A25 A1297.31 V (312.6%)0.0 V2139.95 V (515.65%)1797600.0 WDrop High
6 mm²41 A32 A864.87 V (208.4%)0.0 V1426.63 V (343.77%)1198400.0 WDrop High
10 mm²57 A44 A518.92 V (125.04%)0.0 V855.98 V (206.26%)719040.0 WDrop High
16 mm²76 A59 A324.33 V (78.15%)90.7 V534.99 V (128.91%)449400.0 WDrop High
25 mm²101 A78 A207.57 V (50.02%)207.4 V342.39 V (82.5%)287616.0 WDrop High
35 mm²125 A97 A148.26 V (35.73%)266.7 V244.57 V (58.93%)205440.0 WDrop High
50 mm²151 A118 A103.78 V (25.01%)311.2 V171.2 V (41.25%)143808.0 WDrop High
70 mm²192 A150 A74.13 V (17.86%)340.9 V122.28 V (29.47%)102720.0 WDrop High
95 mm²232 A181 A54.62 V (13.16%)360.4 V90.1 V (21.71%)75688.4 WDrop High
120 mm²269 A210 A43.24 V (10.42%)371.8 V71.33 V (17.19%)59920.0 WDrop High
150 mm²309 A241 A34.59 V (8.34%)380.4 V57.07 V (13.75%)47936.0 WDrop High
185 mm²353 A275 A28.05 V (6.76%)387.0 V46.27 V (11.15%)38867.0 WDrop High
240 mm²415 A324 A21.62 V (5.21%)393.4 V35.67 V (8.59%)29960.0 WDrop High
300 mm²477 A372 A17.3 V (4.17%)397.7 V28.53 V (6.88%)23968.0 WDrop High
400 mm²570 A445 A12.97 V (3.13%)402.0 V21.4 V (5.16%)17976.0 WDrop High

FAQ — 800 Amp Cable Size at 175 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 800A at 175 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 800A over 175m at 415V (voltage drop: 6.49V or 1.56%).

What is the power capacity of 800A at 415V?

At unity power factor, 800A at 415V supports 575.04 kW with a standard 800A circuit breaker.