800 Amp Cable Size at 600 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 800 A over 600 m (1968.5 ft).

Copper Cable (≤3% Drop)4× 400 mm²Drop: 11.12V (2.68%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 73.37V (17.68%)
Voltage at Load403.9 VLine Loss: 15408.0 W
Max Power & Breaker575.04 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 800A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A11861.08 V (2858.09%)0.0 V19565.25 V (4714.52%)16435200.0 WDrop High
2.5 mm²24 A18 A7116.65 V (1714.86%)0.0 V11739.15 V (2828.71%)9861120.0 WDrop High
4 mm²32 A25 A4447.91 V (1071.78%)0.0 V7336.97 V (1767.94%)6163200.0 WDrop High
6 mm²41 A32 A2965.27 V (714.52%)0.0 V4891.31 V (1178.63%)4108800.0 WDrop High
10 mm²57 A44 A1779.16 V (428.71%)0.0 V2934.79 V (707.18%)2465280.0 WDrop High
16 mm²76 A59 A1111.98 V (267.95%)0.0 V1834.24 V (441.99%)1540800.0 WDrop High
25 mm²101 A78 A711.67 V (171.49%)0.0 V1173.91 V (282.87%)986112.0 WDrop High
35 mm²125 A97 A508.33 V (122.49%)0.0 V838.51 V (202.05%)704365.7 WDrop High
50 mm²151 A118 A355.83 V (85.74%)59.2 V586.96 V (141.44%)493056.0 WDrop High
70 mm²192 A150 A254.17 V (61.24%)160.8 V419.26 V (101.03%)352182.9 WDrop High
95 mm²232 A181 A187.28 V (45.13%)227.7 V308.92 V (74.44%)259503.2 WDrop High
120 mm²269 A210 A148.26 V (35.73%)266.7 V244.57 V (58.93%)205440.0 WDrop High
150 mm²309 A241 A118.61 V (28.58%)296.4 V195.65 V (47.15%)164352.0 WDrop High
185 mm²353 A275 A96.17 V (23.17%)318.8 V158.64 V (38.23%)133258.4 WDrop High
240 mm²415 A324 A74.13 V (17.86%)340.9 V122.28 V (29.47%)102720.0 WDrop High
300 mm²477 A372 A59.31 V (14.29%)355.7 V97.83 V (23.57%)82176.0 WDrop High
400 mm²570 A445 A44.48 V (10.72%)370.5 V73.37 V (17.68%)61632.0 WDrop High

FAQ — 800 Amp Cable Size at 600 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 800A at 600 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 4× 400 mm² copper cable for 800A over 600m at 415V (voltage drop: 11.12V or 2.68%).

What is the power capacity of 800A at 415V?

At unity power factor, 800A at 415V supports 575.04 kW with a standard 800A circuit breaker.