800 Amp Cable Size at 80 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 800 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 2.96V (0.71%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 9.78V (2.36%)
Voltage at Load412.0 VLine Loss: 4108.8 W
Max Power & Breaker575.04 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 800A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1581.48 V (381.08%)0.0 V2608.7 V (628.6%)2191360.0 WDrop High
2.5 mm²24 A18 A948.89 V (228.65%)0.0 V1565.22 V (377.16%)1314816.0 WDrop High
4 mm²32 A25 A593.05 V (142.9%)0.0 V978.26 V (235.73%)821760.0 WDrop High
6 mm²41 A32 A395.37 V (95.27%)19.6 V652.17 V (157.15%)547840.0 WDrop High
10 mm²57 A44 A237.22 V (57.16%)177.8 V391.3 V (94.29%)328704.0 WDrop High
16 mm²76 A59 A148.26 V (35.73%)266.7 V244.57 V (58.93%)205440.0 WDrop High
25 mm²101 A78 A94.89 V (22.86%)320.1 V156.52 V (37.72%)131481.6 WDrop High
35 mm²125 A97 A67.78 V (16.33%)347.2 V111.8 V (26.94%)93915.4 WDrop High
50 mm²151 A118 A47.44 V (11.43%)367.6 V78.26 V (18.86%)65740.8 WDrop High
70 mm²192 A150 A33.89 V (8.17%)381.1 V55.9 V (13.47%)46957.7 WDrop High
95 mm²232 A181 A24.97 V (6.02%)390.0 V41.19 V (9.93%)34600.4 WDrop High
120 mm²269 A210 A19.77 V (4.76%)395.2 V32.61 V (7.86%)27392.0 WDrop High
150 mm²309 A241 A15.81 V (3.81%)399.2 V26.09 V (6.29%)21913.6 WDrop High
185 mm²353 A275 A12.82 V (3.09%)402.2 V21.15 V (5.1%)17767.8 WDrop High
240 mm²415 A324 A9.88 V (2.38%)405.1 V16.3 V (3.93%)13696.0 WDrop High
300 mm²477 A372 A7.91 V (1.91%)407.1 V13.04 V (3.14%)10956.8 WDrop High
400 mm²570 A445 A5.93 V (1.43%)409.1 V9.78 V (2.36%)8217.6 WDrop High

FAQ — 800 Amp Cable Size at 80 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 800A at 80 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 800A over 80m at 415V (voltage drop: 2.96V or 0.71%).

What is the power capacity of 800A at 415V?

At unity power factor, 800A at 415V supports 575.04 kW with a standard 800A circuit breaker.