800 Amp Cable Size at 80 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 800 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 2.96V (0.43%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 9.78V (1.42%)
Voltage at Load687.0 VLine Loss: 4108.8 W
Max Power & Breaker956.09 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 800A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1581.48 V (229.2%)0.0 V2608.7 V (378.07%)2191360.0 WDrop High
2.5 mm²24 A18 A948.89 V (137.52%)0.0 V1565.22 V (226.84%)1314816.0 WDrop High
4 mm²32 A25 A593.05 V (85.95%)96.9 V978.26 V (141.78%)821760.0 WDrop High
6 mm²41 A32 A395.37 V (57.3%)294.6 V652.17 V (94.52%)547840.0 WDrop High
10 mm²57 A44 A237.22 V (34.38%)452.8 V391.3 V (56.71%)328704.0 WDrop High
16 mm²76 A59 A148.26 V (21.49%)541.7 V244.57 V (35.44%)205440.0 WDrop High
25 mm²101 A78 A94.89 V (13.75%)595.1 V156.52 V (22.68%)131481.6 WDrop High
35 mm²125 A97 A67.78 V (9.82%)622.2 V111.8 V (16.2%)93915.4 WDrop High
50 mm²151 A118 A47.44 V (6.88%)642.6 V78.26 V (11.34%)65740.8 WDrop High
70 mm²192 A150 A33.89 V (4.91%)656.1 V55.9 V (8.1%)46957.7 WDrop High
95 mm²232 A181 A24.97 V (3.62%)665.0 V41.19 V (5.97%)34600.4 WDrop High
120 mm²269 A210 A19.77 V (2.86%)670.2 V32.61 V (4.73%)27392.0 WDrop High
150 mm²309 A241 A15.81 V (2.29%)674.2 V26.09 V (3.78%)21913.6 WDrop High
185 mm²353 A275 A12.82 V (1.86%)677.2 V21.15 V (3.07%)17767.8 WDrop High
240 mm²415 A324 A9.88 V (1.43%)680.1 V16.3 V (2.36%)13696.0 WDrop High
300 mm²477 A372 A7.91 V (1.15%)682.1 V13.04 V (1.89%)10956.8 WDrop High
400 mm²570 A445 A5.93 V (0.86%)684.1 V9.78 V (1.42%)8217.6 WDrop High

FAQ — 800 Amp Cable Size at 80 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 800A at 80 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 800A over 80m at 690V (voltage drop: 2.96V or 0.43%).

What is the power capacity of 800A at 690V?

At unity power factor, 800A at 690V supports 956.09 kW with a standard 800A circuit breaker.