90 Amp Cable Size at 90 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 90 A over 90 m (295.3 ft).

Copper Cable (≤3% Drop)25 mm²Drop: 12.01V (1.74%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 14.15V (2.05%)
Voltage at Load678.0 VLine Loss: 1872.1 W
Max Power & Breaker107.56 kW90A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 90A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A200.16 V (29.01%)489.8 V330.16 V (47.85%)31201.2 WDrop High
2.5 mm²24 A18 A120.09 V (17.4%)569.9 V198.1 V (28.71%)18720.7 WDrop High
4 mm²32 A25 A75.06 V (10.88%)614.9 V123.81 V (17.94%)11700.4 WDrop High
6 mm²41 A32 A50.04 V (7.25%)640.0 V82.54 V (11.96%)7800.3 WDrop High
10 mm²57 A44 A30.02 V (4.35%)660.0 V49.52 V (7.18%)4680.2 WDrop High
16 mm²76 A59 A18.76 V (2.72%)671.2 V30.95 V (4.49%)2925.1 WDrop High
25 mm²101 A78 A12.01 V (1.74%)678.0 V19.81 V (2.87%)1872.1 W✓ OK (≤3%)
35 mm²125 A97 A8.58 V (1.24%)681.4 V14.15 V (2.05%)1337.2 W✓ OK (≤3%)
50 mm²151 A118 A6.0 V (0.87%)684.0 V9.9 V (1.44%)936.0 W✓ OK (≤3%)
70 mm²192 A150 A4.29 V (0.62%)685.7 V7.07 V (1.03%)668.6 W✓ OK (≤3%)
95 mm²232 A181 A3.16 V (0.46%)686.8 V5.21 V (0.76%)492.7 W✓ OK (≤3%)
120 mm²269 A210 A2.5 V (0.36%)687.5 V4.13 V (0.6%)390.0 W✓ OK (≤3%)
150 mm²309 A241 A2.0 V (0.29%)688.0 V3.3 V (0.48%)312.0 W✓ OK (≤3%)
185 mm²353 A275 A1.62 V (0.24%)688.4 V2.68 V (0.39%)253.0 W✓ OK (≤3%)
240 mm²415 A324 A1.25 V (0.18%)688.7 V2.06 V (0.3%)195.0 W✓ OK (≤3%)
300 mm²477 A372 A1.0 V (0.15%)689.0 V1.65 V (0.24%)156.0 W✓ OK (≤3%)
400 mm²570 A445 A0.75 V (0.11%)689.2 V1.24 V (0.18%)117.0 W✓ OK (≤3%)

FAQ — 90 Amp Cable Size at 90 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 90A at 90 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 25 mm² copper cable for 90A over 90m at 690V (voltage drop: 12.01V or 1.74%).

What is the power capacity of 90A at 690V?

At unity power factor, 90A at 690V supports 107.56 kW with a standard 90A circuit breaker.