900 Amp Cable Size at 175 Meters (400V Three-Phase (IEC European Grid))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 900 A over 175 m (574.1 ft).
Copper Cable (≤3% Drop)2× 400 mm²Drop: 7.29V (1.82%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 24.07V (6.02%)
Voltage at Load392.7 VLine Loss: 11375.5 W
Max Power & Breaker623.54 kW1000A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 900A at 175m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 3891.92 V (972.98%) | 0.0 V | 6419.85 V (1604.96%) | 6066900.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 2335.15 V (583.79%) | 0.0 V | 3851.91 V (962.98%) | 3640140.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 1459.47 V (364.87%) | 0.0 V | 2407.44 V (601.86%) | 2275087.5 W | Drop High |
| 6 mm² | 41 A | 32 A | 972.98 V (243.24%) | 0.0 V | 1604.96 V (401.24%) | 1516725.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 583.79 V (145.95%) | 0.0 V | 962.98 V (240.74%) | 910035.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 364.87 V (91.22%) | 35.1 V | 601.86 V (150.47%) | 568771.9 W | Drop High |
| 25 mm² | 101 A | 78 A | 233.52 V (58.38%) | 166.5 V | 385.19 V (96.3%) | 364014.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 166.8 V (41.7%) | 233.2 V | 275.14 V (68.78%) | 260010.0 W | Drop High |
| 50 mm² | 151 A | 118 A | 116.76 V (29.19%) | 283.2 V | 192.6 V (48.15%) | 182007.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 83.4 V (20.85%) | 316.6 V | 137.57 V (34.39%) | 130005.0 W | Drop High |
| 95 mm² | 232 A | 181 A | 61.45 V (15.36%) | 338.5 V | 101.37 V (25.34%) | 95793.2 W | Drop High |
| 120 mm² | 269 A | 210 A | 48.65 V (12.16%) | 351.4 V | 80.25 V (20.06%) | 75836.2 W | Drop High |
| 150 mm² | 309 A | 241 A | 38.92 V (9.73%) | 361.1 V | 64.2 V (16.05%) | 60669.0 W | Drop High |
| 185 mm² | 353 A | 275 A | 31.56 V (7.89%) | 368.4 V | 52.05 V (13.01%) | 49191.1 W | Drop High |
| 240 mm² | 415 A | 324 A | 24.32 V (6.08%) | 375.7 V | 40.12 V (10.03%) | 37918.1 W | Drop High |
| 300 mm² | 477 A | 372 A | 19.46 V (4.86%) | 380.5 V | 32.1 V (8.02%) | 30334.5 W | Drop High |
| 400 mm² | 570 A | 445 A | 14.59 V (3.65%) | 385.4 V | 24.07 V (6.02%) | 22750.9 W | Drop High |
FAQ — 900 Amp Cable Size at 175 Meters (400V Three-Phase (IEC European Grid))
What mm² cable size is required for 900A at 175 meters (400V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 900A over 175m at 400V (voltage drop: 7.29V or 1.82%).
What is the power capacity of 900A at 400V?
At unity power factor, 900A at 400V supports 623.54 kW with a standard 1000A circuit breaker.
Related Lengths & Currents (400V)
900A · 5m (400V)900A · 10m (400V)900A · 15m (400V)900A · 20m (400V)900A · 25m (400V)900A · 30m (400V)900A · 35m (400V)900A · 40m (400V)900A · 45m (400V)900A · 50m (400V)900A · 60m (400V)900A · 70m (400V)10A · 175m (400V)16A · 175m (400V)20A · 175m (400V)25A · 175m (400V)32A · 175m (400V)40A · 175m (400V)50A · 175m (400V)63A · 175m (400V)80A · 175m (400V)100A · 175m (400V)125A · 175m (400V)160A · 175m (400V)200A · 175m (400V)