Kabeltværsnit for 175 Ampere ved 100 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 175 A over 100 m ved 230V.

Copper Cable (≤3% Drop)120 mm²Drop: 6.24V (2.71%)
Aluminum Cable (≤3% Drop)185 mm²Drop: 6.68V (2.9%)
Voltage at Load223.8 VLine Loss: 1092.3 W
Max Power & Breaker40.25 kW175A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 100m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A499.33 V (217.1%)0.0 V823.67 V (358.12%)87383.3 WDrop High
2.5 mm²24 A18 A299.6 V (130.26%)0.0 V494.2 V (214.87%)52430.0 WDrop High
4 mm²32 A25 A187.25 V (81.41%)42.8 V308.88 V (134.29%)32768.7 WDrop High
6 mm²41 A32 A124.83 V (54.28%)105.2 V205.92 V (89.53%)21845.8 WDrop High
10 mm²57 A44 A74.9 V (32.57%)155.1 V123.55 V (53.72%)13107.5 WDrop High
16 mm²76 A59 A46.81 V (20.35%)183.2 V77.22 V (33.57%)8192.2 WDrop High
25 mm²101 A78 A29.96 V (13.03%)200.0 V49.42 V (21.49%)5243.0 WDrop High
35 mm²125 A97 A21.4 V (9.3%)208.6 V35.3 V (15.35%)3745.0 WDrop High
50 mm²151 A118 A14.98 V (6.51%)215.0 V24.71 V (10.74%)2621.5 WDrop High
70 mm²192 A150 A10.7 V (4.65%)219.3 V17.65 V (7.67%)1872.5 W~ ≤5%
95 mm²232 A181 A7.88 V (3.43%)222.1 V13.01 V (5.65%)1379.7 W~ ≤5%
120 mm²269 A210 A6.24 V (2.71%)223.8 V10.3 V (4.48%)1092.3 W✓ OK (≤3%)
150 mm²309 A241 A4.99 V (2.17%)225.0 V8.24 V (3.58%)873.8 W✓ OK (≤3%)
185 mm²353 A275 A4.05 V (1.76%)226.0 V6.68 V (2.9%)708.5 W✓ OK (≤3%)
240 mm²415 A324 A3.12 V (1.36%)226.9 V5.15 V (2.24%)546.1 W✓ OK (≤3%)
300 mm²477 A372 A2.5 V (1.09%)227.5 V4.12 V (1.79%)436.9 W✓ OK (≤3%)
400 mm²570 A445 A1.87 V (0.81%)228.1 V3.09 V (1.34%)327.7 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 175 Ampere ved 100 Meter (230V)

Hvilket kabeltværsnit kræves til 175A ved 100 meter (230V)?

Til 175 Ampere over 100 meter ved 230V anbefales 120 mm² kobberkabel (spændingsfald 6.24V / 2.71%).

Hvor mange kW svarer 175A ved 230V til?

Det svarer til 40.25 kW med en anbefalet sikring på 175A.