Kabeltværsnit for 35 Ampere ved 175 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 35 A over 175 m ved 400V.

Copper Cable (≤3% Drop)25 mm²Drop: 9.08V (2.27%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 10.7V (2.67%)
Voltage at Load390.9 VLine Loss: 550.5 W
Max Power & Breaker24.25 kW35A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 35A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A151.35 V (37.84%)248.6 V249.66 V (62.42%)9175.2 WDrop High
2.5 mm²24 A18 A90.81 V (22.7%)309.2 V149.8 V (37.45%)5505.1 WDrop High
4 mm²32 A25 A56.76 V (14.19%)343.2 V93.62 V (23.41%)3440.7 WDrop High
6 mm²41 A32 A37.84 V (9.46%)362.2 V62.42 V (15.6%)2293.8 WDrop High
10 mm²57 A44 A22.7 V (5.68%)377.3 V37.45 V (9.36%)1376.3 WDrop High
16 mm²76 A59 A14.19 V (3.55%)385.8 V23.41 V (5.85%)860.2 W~ ≤5%
25 mm²101 A78 A9.08 V (2.27%)390.9 V14.98 V (3.74%)550.5 W✓ OK (≤3%)
35 mm²125 A97 A6.49 V (1.62%)393.5 V10.7 V (2.67%)393.2 W✓ OK (≤3%)
50 mm²151 A118 A4.54 V (1.14%)395.5 V7.49 V (1.87%)275.3 W✓ OK (≤3%)
70 mm²192 A150 A3.24 V (0.81%)396.8 V5.35 V (1.34%)196.6 W✓ OK (≤3%)
95 mm²232 A181 A2.39 V (0.6%)397.6 V3.94 V (0.99%)144.9 W✓ OK (≤3%)
120 mm²269 A210 A1.89 V (0.47%)398.1 V3.12 V (0.78%)114.7 W✓ OK (≤3%)
150 mm²309 A241 A1.51 V (0.38%)398.5 V2.5 V (0.62%)91.8 W✓ OK (≤3%)
185 mm²353 A275 A1.23 V (0.31%)398.8 V2.02 V (0.51%)74.4 W✓ OK (≤3%)
240 mm²415 A324 A0.95 V (0.24%)399.1 V1.56 V (0.39%)57.3 W✓ OK (≤3%)
300 mm²477 A372 A0.76 V (0.19%)399.2 V1.25 V (0.31%)45.9 W✓ OK (≤3%)
400 mm²570 A445 A0.57 V (0.14%)399.4 V0.94 V (0.23%)34.4 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 35 Ampere ved 175 Meter (400V)

Hvilket kabeltværsnit kræves til 35A ved 175 meter (400V)?

Til 35 Ampere over 175 meter ved 400V anbefales 25 mm² kobberkabel (spændingsfald 9.08V / 2.27%).

Hvor mange kW svarer 35A ved 400V til?

Det svarer til 24.25 kW med en anbefalet sikring på 35A.