Kabeltværsnit for 475 Ampere ved 500 Meter (230V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 475 A over 500 m ved 230V.
Copper Cable (≤3% Drop)4× 400 mm²Drop: 6.35V (2.76%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 41.92V (18.23%)
Voltage at Load223.7 VLine Loss: 3017.7 W
Max Power & Breaker109.25 kW500A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 475A at 500m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 6776.67 V (2946.38%) | 0.0 V | 11178.33 V (4860.14%) | 3218916.7 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 4066.0 V (1767.83%) | 0.0 V | 6707.0 V (2916.09%) | 1931350.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 2541.25 V (1104.89%) | 0.0 V | 4191.88 V (1822.55%) | 1207093.8 W | Drop High |
| 6 mm² | 41 A | 32 A | 1694.17 V (736.59%) | 0.0 V | 2794.58 V (1215.04%) | 804729.2 W | Drop High |
| 10 mm² | 57 A | 44 A | 1016.5 V (441.96%) | 0.0 V | 1676.75 V (729.02%) | 482837.5 W | Drop High |
| 16 mm² | 76 A | 59 A | 635.31 V (276.22%) | 0.0 V | 1047.97 V (455.64%) | 301773.4 W | Drop High |
| 25 mm² | 101 A | 78 A | 406.6 V (176.78%) | 0.0 V | 670.7 V (291.61%) | 193135.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 290.43 V (126.27%) | 0.0 V | 479.07 V (208.29%) | 137953.6 W | Drop High |
| 50 mm² | 151 A | 118 A | 203.3 V (88.39%) | 26.7 V | 335.35 V (145.8%) | 96567.5 W | Drop High |
| 70 mm² | 192 A | 150 A | 145.21 V (63.14%) | 84.8 V | 239.54 V (104.15%) | 68976.8 W | Drop High |
| 95 mm² | 232 A | 181 A | 107.0 V (46.52%) | 123.0 V | 176.5 V (76.74%) | 50825.0 W | Drop High |
| 120 mm² | 269 A | 210 A | 84.71 V (36.83%) | 145.3 V | 139.73 V (60.75%) | 40236.5 W | Drop High |
| 150 mm² | 309 A | 241 A | 67.77 V (29.46%) | 162.2 V | 111.78 V (48.6%) | 32189.2 W | Drop High |
| 185 mm² | 353 A | 275 A | 54.95 V (23.89%) | 175.1 V | 90.64 V (39.41%) | 26099.3 W | Drop High |
| 240 mm² | 415 A | 324 A | 42.35 V (18.41%) | 187.6 V | 69.86 V (30.38%) | 20118.2 W | Drop High |
| 300 mm² | 477 A | 372 A | 33.88 V (14.73%) | 196.1 V | 55.89 V (24.3%) | 16094.6 W | Drop High |
| 400 mm² | 570 A | 445 A | 25.41 V (11.05%) | 204.6 V | 41.92 V (18.23%) | 12070.9 W | Drop High |
FAQ — Kabeltværsnit for 475 Ampere ved 500 Meter (230V)
Hvilket kabeltværsnit kræves til 475A ved 500 meter (230V)?
Til 475 Ampere over 500 meter ved 230V anbefales 4× 400 mm² kobberkabel (spændingsfald 6.35V / 2.76%).
Hvor mange kW svarer 475A ved 230V til?
Det svarer til 109.25 kW med en anbefalet sikring på 500A.
Related Lengths & Currents (230V)
475A · 5m (230V)475A · 10m (230V)475A · 15m (230V)475A · 20m (230V)475A · 25m (230V)475A · 30m (230V)475A · 35m (230V)475A · 40m (230V)475A · 45m (230V)475A · 50m (230V)475A · 60m (230V)475A · 70m (230V)10A · 500m (230V)16A · 500m (230V)20A · 500m (230V)25A · 500m (230V)32A · 500m (230V)40A · 500m (230V)50A · 500m (230V)63A · 500m (230V)80A · 500m (230V)100A · 500m (230V)125A · 500m (230V)160A · 500m (230V)200A · 500m (230V)