⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 15 Ampere vid 120 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 15 A över 120 m vid 230V.

Copper Cable (≤3% Drop)16 mm²Drop: 4.82V (2.09%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 5.08V (2.21%)
Voltage at Load225.2 VLine Loss: 72.2 W
Max Power & Breaker3.45 kW15A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A51.36 V (22.33%)178.6 V84.72 V (36.83%)770.4 WDrop High
2.5 mm²24 A18 A30.82 V (13.4%)199.2 V50.83 V (22.1%)462.2 WDrop High
4 mm²32 A25 A19.26 V (8.37%)210.7 V31.77 V (13.81%)288.9 WDrop High
6 mm²41 A32 A12.84 V (5.58%)217.2 V21.18 V (9.21%)192.6 WDrop High
10 mm²57 A44 A7.7 V (3.35%)222.3 V12.71 V (5.53%)115.6 W~ ≤5%
16 mm²76 A59 A4.82 V (2.09%)225.2 V7.94 V (3.45%)72.2 W✓ OK (≤3%)
25 mm²101 A78 A3.08 V (1.34%)226.9 V5.08 V (2.21%)46.2 W✓ OK (≤3%)
35 mm²125 A97 A2.2 V (0.96%)227.8 V3.63 V (1.58%)33.0 W✓ OK (≤3%)
50 mm²151 A118 A1.54 V (0.67%)228.5 V2.54 V (1.11%)23.1 W✓ OK (≤3%)
70 mm²192 A150 A1.1 V (0.48%)228.9 V1.82 V (0.79%)16.5 W✓ OK (≤3%)
95 mm²232 A181 A0.81 V (0.35%)229.2 V1.34 V (0.58%)12.2 W✓ OK (≤3%)
120 mm²269 A210 A0.64 V (0.28%)229.4 V1.06 V (0.46%)9.6 W✓ OK (≤3%)
150 mm²309 A241 A0.51 V (0.22%)229.5 V0.85 V (0.37%)7.7 W✓ OK (≤3%)
185 mm²353 A275 A0.42 V (0.18%)229.6 V0.69 V (0.3%)6.2 W✓ OK (≤3%)
240 mm²415 A324 A0.32 V (0.14%)229.7 V0.53 V (0.23%)4.8 W✓ OK (≤3%)
300 mm²477 A372 A0.26 V (0.11%)229.7 V0.42 V (0.18%)3.9 W✓ OK (≤3%)
400 mm²570 A445 A0.19 V (0.08%)229.8 V0.32 V (0.14%)2.9 W✓ OK (≤3%)

FAQ — Kabelarea för 15 Ampere vid 120 Meter (230V)

Vilken kabelarea krävs för 15A vid 120 meter (230V)?

För 15 Ampere över 120 meter vid 230V rekommenderas 16 mm² kopparkabel för att hålla spänningsfallet under 3% (4.82V / 2.09%).

Hur stor effekt motsvarar 15A vid 230V?

Det motsvarar 3.45 kW med en rekommenderad säkring på 15A.