Kabelarea för 15 Ampere vid 90 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 15 A över 90 m vid 400V.

Copper Cable (≤3% Drop)6 mm²Drop: 8.34V (2.08%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 8.25V (2.06%)
Voltage at Load391.7 VLine Loss: 216.7 W
Max Power & Breaker10.39 kW15A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A33.36 V (8.34%)366.6 V55.03 V (13.76%)866.7 WDrop High
2.5 mm²24 A18 A20.02 V (5.0%)380.0 V33.02 V (8.25%)520.0 WDrop High
4 mm²32 A25 A12.51 V (3.13%)387.5 V20.64 V (5.16%)325.0 W~ ≤5%
6 mm²41 A32 A8.34 V (2.08%)391.7 V13.76 V (3.44%)216.7 W✓ OK (≤3%)
10 mm²57 A44 A5.0 V (1.25%)395.0 V8.25 V (2.06%)130.0 W✓ OK (≤3%)
16 mm²76 A59 A3.13 V (0.78%)396.9 V5.16 V (1.29%)81.3 W✓ OK (≤3%)
25 mm²101 A78 A2.0 V (0.5%)398.0 V3.3 V (0.83%)52.0 W✓ OK (≤3%)
35 mm²125 A97 A1.43 V (0.36%)398.6 V2.36 V (0.59%)37.1 W✓ OK (≤3%)
50 mm²151 A118 A1.0 V (0.25%)399.0 V1.65 V (0.41%)26.0 W✓ OK (≤3%)
70 mm²192 A150 A0.71 V (0.18%)399.3 V1.18 V (0.29%)18.6 W✓ OK (≤3%)
95 mm²232 A181 A0.53 V (0.13%)399.5 V0.87 V (0.22%)13.7 W✓ OK (≤3%)
120 mm²269 A210 A0.42 V (0.1%)399.6 V0.69 V (0.17%)10.8 W✓ OK (≤3%)
150 mm²309 A241 A0.33 V (0.08%)399.7 V0.55 V (0.14%)8.7 W✓ OK (≤3%)
185 mm²353 A275 A0.27 V (0.07%)399.7 V0.45 V (0.11%)7.0 W✓ OK (≤3%)
240 mm²415 A324 A0.21 V (0.05%)399.8 V0.34 V (0.09%)5.4 W✓ OK (≤3%)
300 mm²477 A372 A0.17 V (0.04%)399.8 V0.28 V (0.07%)4.3 W✓ OK (≤3%)
400 mm²570 A445 A0.13 V (0.03%)399.9 V0.21 V (0.05%)3.3 W✓ OK (≤3%)

FAQ — Kabelarea för 15 Ampere vid 90 Meter (400V)

Vilken kabelarea krävs för 15A vid 90 meter (400V)?

För 15 Ampere över 90 meter vid 400V rekommenderas 6 mm² kopparkabel för att hålla spänningsfallet under 3% (8.34V / 2.08%).

Hur stor effekt motsvarar 15A vid 400V?

Det motsvarar 10.39 kW med en rekommenderad säkring på 15A.