Kabelarea för 225 Ampere vid 200 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 225 A över 200 m vid 230V.

Copper Cable (≤3% Drop)300 mm²Drop: 6.42V (2.79%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 7.94V (3.45%)
Voltage at Load223.6 VLine Loss: 1444.5 W
Max Power & Breaker51.75 kW225A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 200m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1284.0 V (558.26%)0.0 V2118.0 V (920.87%)288900.0 WDrop High
2.5 mm²24 A18 A770.4 V (334.96%)0.0 V1270.8 V (552.52%)173340.0 WDrop High
4 mm²32 A25 A481.5 V (209.35%)0.0 V794.25 V (345.33%)108337.5 WDrop High
6 mm²41 A32 A321.0 V (139.57%)0.0 V529.5 V (230.22%)72225.0 WDrop High
10 mm²57 A44 A192.6 V (83.74%)37.4 V317.7 V (138.13%)43335.0 WDrop High
16 mm²76 A59 A120.37 V (52.34%)109.6 V198.56 V (86.33%)27084.4 WDrop High
25 mm²101 A78 A77.04 V (33.5%)153.0 V127.08 V (55.25%)17334.0 WDrop High
35 mm²125 A97 A55.03 V (23.93%)175.0 V90.77 V (39.47%)12381.4 WDrop High
50 mm²151 A118 A38.52 V (16.75%)191.5 V63.54 V (27.63%)8667.0 WDrop High
70 mm²192 A150 A27.51 V (11.96%)202.5 V45.39 V (19.73%)6190.7 WDrop High
95 mm²232 A181 A20.27 V (8.81%)209.7 V33.44 V (14.54%)4561.6 WDrop High
120 mm²269 A210 A16.05 V (6.98%)213.9 V26.47 V (11.51%)3611.2 WDrop High
150 mm²309 A241 A12.84 V (5.58%)217.2 V21.18 V (9.21%)2889.0 WDrop High
185 mm²353 A275 A10.41 V (4.53%)219.6 V17.17 V (7.47%)2342.4 W~ ≤5%
240 mm²415 A324 A8.02 V (3.49%)222.0 V13.24 V (5.76%)1805.6 W~ ≤5%
300 mm²477 A372 A6.42 V (2.79%)223.6 V10.59 V (4.6%)1444.5 W✓ OK (≤3%)
400 mm²570 A445 A4.81 V (2.09%)225.2 V7.94 V (3.45%)1083.4 W✓ OK (≤3%)

FAQ — Kabelarea för 225 Ampere vid 200 Meter (230V)

Vilken kabelarea krävs för 225A vid 200 meter (230V)?

För 225 Ampere över 200 meter vid 230V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (6.42V / 2.79%).

Hur stor effekt motsvarar 225A vid 230V?

Det motsvarar 51.75 kW med en rekommenderad säkring på 225A.