Kabelarea för 225 Ampere vid 250 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 225 A över 250 m vid 230V.

Copper Cable (≤3% Drop)400 mm²Drop: 6.02V (2.62%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 9.93V (4.32%)
Voltage at Load224.0 VLine Loss: 1354.2 W
Max Power & Breaker51.75 kW225A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1605.0 V (697.83%)0.0 V2647.5 V (1151.09%)361125.0 WDrop High
2.5 mm²24 A18 A963.0 V (418.7%)0.0 V1588.5 V (690.65%)216675.0 WDrop High
4 mm²32 A25 A601.88 V (261.68%)0.0 V992.81 V (431.66%)135421.9 WDrop High
6 mm²41 A32 A401.25 V (174.46%)0.0 V661.88 V (287.77%)90281.2 WDrop High
10 mm²57 A44 A240.75 V (104.67%)0.0 V397.12 V (172.66%)54168.7 WDrop High
16 mm²76 A59 A150.47 V (65.42%)79.5 V248.2 V (107.91%)33855.5 WDrop High
25 mm²101 A78 A96.3 V (41.87%)133.7 V158.85 V (69.07%)21667.5 WDrop High
35 mm²125 A97 A68.79 V (29.91%)161.2 V113.46 V (49.33%)15476.8 WDrop High
50 mm²151 A118 A48.15 V (20.93%)181.8 V79.42 V (34.53%)10833.8 WDrop High
70 mm²192 A150 A34.39 V (14.95%)195.6 V56.73 V (24.67%)7738.4 WDrop High
95 mm²232 A181 A25.34 V (11.02%)204.7 V41.8 V (18.18%)5702.0 WDrop High
120 mm²269 A210 A20.06 V (8.72%)209.9 V33.09 V (14.39%)4514.1 WDrop High
150 mm²309 A241 A16.05 V (6.98%)213.9 V26.47 V (11.51%)3611.2 WDrop High
185 mm²353 A275 A13.01 V (5.66%)217.0 V21.47 V (9.33%)2928.0 WDrop High
240 mm²415 A324 A10.03 V (4.36%)220.0 V16.55 V (7.19%)2257.0 W~ ≤5%
300 mm²477 A372 A8.03 V (3.49%)222.0 V13.24 V (5.76%)1805.6 W~ ≤5%
400 mm²570 A445 A6.02 V (2.62%)224.0 V9.93 V (4.32%)1354.2 W✓ OK (≤3%)

FAQ — Kabelarea för 225 Ampere vid 250 Meter (230V)

Vilken kabelarea krävs för 225A vid 250 meter (230V)?

För 225 Ampere över 250 meter vid 230V rekommenderas 400 mm² kopparkabel för att hålla spänningsfallet under 3% (6.02V / 2.62%).

Hur stor effekt motsvarar 225A vid 230V?

Det motsvarar 51.75 kW med en rekommenderad säkring på 225A.