Kabelarea för 250 Ampere vid 175 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 250 A över 175 m vid 400V.

Copper Cable (≤3% Drop)150 mm²Drop: 10.81V (2.7%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 11.15V (2.79%)
Voltage at Load389.2 VLine Loss: 4681.2 W
Max Power & Breaker173.21 kW250A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 250A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1081.09 V (270.27%)0.0 V1783.29 V (445.82%)468125.0 WDrop High
2.5 mm²24 A18 A648.65 V (162.16%)0.0 V1069.97 V (267.49%)280875.0 WDrop High
4 mm²32 A25 A405.41 V (101.35%)0.0 V668.73 V (167.18%)175546.9 WDrop High
6 mm²41 A32 A270.27 V (67.57%)129.7 V445.82 V (111.46%)117031.2 WDrop High
10 mm²57 A44 A162.16 V (40.54%)237.8 V267.49 V (66.87%)70218.7 WDrop High
16 mm²76 A59 A101.35 V (25.34%)298.6 V167.18 V (41.8%)43886.7 WDrop High
25 mm²101 A78 A64.87 V (16.22%)335.1 V107.0 V (26.75%)28087.5 WDrop High
35 mm²125 A97 A46.33 V (11.58%)353.7 V76.43 V (19.11%)20062.5 WDrop High
50 mm²151 A118 A32.43 V (8.11%)367.6 V53.5 V (13.37%)14043.7 WDrop High
70 mm²192 A150 A23.17 V (5.79%)376.8 V38.21 V (9.55%)10031.2 WDrop High
95 mm²232 A181 A17.07 V (4.27%)382.9 V28.16 V (7.04%)7391.4 WDrop High
120 mm²269 A210 A13.51 V (3.38%)386.5 V22.29 V (5.57%)5851.6 W~ ≤5%
150 mm²309 A241 A10.81 V (2.7%)389.2 V17.83 V (4.46%)4681.2 W✓ OK (≤3%)
185 mm²353 A275 A8.77 V (2.19%)391.2 V14.46 V (3.61%)3795.6 W✓ OK (≤3%)
240 mm²415 A324 A6.76 V (1.69%)393.2 V11.15 V (2.79%)2925.8 W✓ OK (≤3%)
300 mm²477 A372 A5.41 V (1.35%)394.6 V8.92 V (2.23%)2340.6 W✓ OK (≤3%)
400 mm²570 A445 A4.05 V (1.01%)395.9 V6.69 V (1.67%)1755.5 W✓ OK (≤3%)

FAQ — Kabelarea för 250 Ampere vid 175 Meter (400V)

Vilken kabelarea krävs för 250A vid 175 meter (400V)?

För 250 Ampere över 175 meter vid 400V rekommenderas 150 mm² kopparkabel för att hålla spänningsfallet under 3% (10.81V / 2.7%).

Hur stor effekt motsvarar 250A vid 400V?

Det motsvarar 173.21 kW med en rekommenderad säkring på 250A.