Kabelarea för 275 Ampere vid 300 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 275 A över 300 m vid 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 10.19V (2.55%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 12.61V (3.15%)
Voltage at Load389.8 VLine Loss: 4855.1 W
Max Power & Breaker190.53 kW300A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 275A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2038.62 V (509.66%)0.0 V3362.78 V (840.69%)971025.0 WDrop High
2.5 mm²24 A18 A1223.17 V (305.79%)0.0 V2017.67 V (504.42%)582615.0 WDrop High
4 mm²32 A25 A764.48 V (191.12%)0.0 V1261.04 V (315.26%)364134.4 WDrop High
6 mm²41 A32 A509.66 V (127.41%)0.0 V840.69 V (210.17%)242756.2 WDrop High
10 mm²57 A44 A305.79 V (76.45%)94.2 V504.42 V (126.1%)145653.8 WDrop High
16 mm²76 A59 A191.12 V (47.78%)208.9 V315.26 V (78.82%)91033.6 WDrop High
25 mm²101 A78 A122.32 V (30.58%)277.7 V201.77 V (50.44%)58261.5 WDrop High
35 mm²125 A97 A87.37 V (21.84%)312.6 V144.12 V (36.03%)41615.4 WDrop High
50 mm²151 A118 A61.16 V (15.29%)338.8 V100.88 V (25.22%)29130.7 WDrop High
70 mm²192 A150 A43.68 V (10.92%)356.3 V72.06 V (18.01%)20807.7 WDrop High
95 mm²232 A181 A32.19 V (8.05%)367.8 V53.1 V (13.27%)15332.0 WDrop High
120 mm²269 A210 A25.48 V (6.37%)374.5 V42.03 V (10.51%)12137.8 WDrop High
150 mm²309 A241 A20.39 V (5.1%)379.6 V33.63 V (8.41%)9710.2 WDrop High
185 mm²353 A275 A16.53 V (4.13%)383.5 V27.27 V (6.82%)7873.2 W~ ≤5%
240 mm²415 A324 A12.74 V (3.19%)387.3 V21.02 V (5.25%)6068.9 W~ ≤5%
300 mm²477 A372 A10.19 V (2.55%)389.8 V16.81 V (4.2%)4855.1 W✓ OK (≤3%)
400 mm²570 A445 A7.64 V (1.91%)392.4 V12.61 V (3.15%)3641.3 W✓ OK (≤3%)

FAQ — Kabelarea för 275 Ampere vid 300 Meter (400V)

Vilken kabelarea krävs för 275A vid 300 meter (400V)?

För 275 Ampere över 300 meter vid 400V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (10.19V / 2.55%).

Hur stor effekt motsvarar 275A vid 400V?

Det motsvarar 190.53 kW med en rekommenderad säkring på 300A.