Kabelarea för 350 Ampere vid 120 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 350 A över 120 m vid 400V.

Copper Cable (≤3% Drop)185 mm²Drop: 8.41V (2.1%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 8.56V (2.14%)
Voltage at Load391.6 VLine Loss: 5101.3 W
Max Power & Breaker242.49 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 350A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1037.84 V (259.46%)0.0 V1711.96 V (427.99%)629160.0 WDrop High
2.5 mm²24 A18 A622.71 V (155.68%)0.0 V1027.18 V (256.79%)377496.0 WDrop High
4 mm²32 A25 A389.19 V (97.3%)10.8 V641.98 V (160.5%)235935.0 WDrop High
6 mm²41 A32 A259.46 V (64.87%)140.5 V427.99 V (107.0%)157290.0 WDrop High
10 mm²57 A44 A155.68 V (38.92%)244.3 V256.79 V (64.2%)94374.0 WDrop High
16 mm²76 A59 A97.3 V (24.32%)302.7 V160.5 V (40.12%)58983.8 WDrop High
25 mm²101 A78 A62.27 V (15.57%)337.7 V102.72 V (25.68%)37749.6 WDrop High
35 mm²125 A97 A44.48 V (11.12%)355.5 V73.37 V (18.34%)26964.0 WDrop High
50 mm²151 A118 A31.14 V (7.78%)368.9 V51.36 V (12.84%)18874.8 WDrop High
70 mm²192 A150 A22.24 V (5.56%)377.8 V36.68 V (9.17%)13482.0 WDrop High
95 mm²232 A181 A16.39 V (4.1%)383.6 V27.03 V (6.76%)9934.1 WDrop High
120 mm²269 A210 A12.97 V (3.24%)387.0 V21.4 V (5.35%)7864.5 WDrop High
150 mm²309 A241 A10.38 V (2.59%)389.6 V17.12 V (4.28%)6291.6 WDrop High
185 mm²353 A275 A8.41 V (2.1%)391.6 V13.88 V (3.47%)5101.3 W✓ OK (≤3%)
240 mm²415 A324 A6.49 V (1.62%)393.5 V10.7 V (2.67%)3932.2 W✓ OK (≤3%)
300 mm²477 A372 A5.19 V (1.3%)394.8 V8.56 V (2.14%)3145.8 W✓ OK (≤3%)
400 mm²570 A445 A3.89 V (0.97%)396.1 V6.42 V (1.6%)2359.3 W✓ OK (≤3%)

FAQ — Kabelarea för 350 Ampere vid 120 Meter (400V)

Vilken kabelarea krävs för 350A vid 120 meter (400V)?

För 350 Ampere över 120 meter vid 400V rekommenderas 185 mm² kopparkabel för att hålla spänningsfallet under 3% (8.41V / 2.1%).

Hur stor effekt motsvarar 350A vid 400V?

Det motsvarar 242.49 kW med en rekommenderad säkring på 350A.