Kabelarea för 350 Ampere vid 175 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 350 A över 175 m vid 400V.

Copper Cable (≤3% Drop)240 mm²Drop: 9.46V (2.36%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 9.36V (2.34%)
Voltage at Load390.5 VLine Loss: 5734.5 W
Max Power & Breaker242.49 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 350A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1513.52 V (378.38%)0.0 V2496.61 V (624.15%)917525.0 WDrop High
2.5 mm²24 A18 A908.11 V (227.03%)0.0 V1497.96 V (374.49%)550515.0 WDrop High
4 mm²32 A25 A567.57 V (141.89%)0.0 V936.23 V (234.06%)344071.9 WDrop High
6 mm²41 A32 A378.38 V (94.6%)21.6 V624.15 V (156.04%)229381.2 WDrop High
10 mm²57 A44 A227.03 V (56.76%)173.0 V374.49 V (93.62%)137628.7 WDrop High
16 mm²76 A59 A141.89 V (35.47%)258.1 V234.06 V (58.51%)86018.0 WDrop High
25 mm²101 A78 A90.81 V (22.7%)309.2 V149.8 V (37.45%)55051.5 WDrop High
35 mm²125 A97 A64.87 V (16.22%)335.1 V107.0 V (26.75%)39322.5 WDrop High
50 mm²151 A118 A45.41 V (11.35%)354.6 V74.9 V (18.72%)27525.7 WDrop High
70 mm²192 A150 A32.43 V (8.11%)367.6 V53.5 V (13.37%)19661.2 WDrop High
95 mm²232 A181 A23.9 V (5.97%)376.1 V39.42 V (9.86%)14487.2 WDrop High
120 mm²269 A210 A18.92 V (4.73%)381.1 V31.21 V (7.8%)11469.1 WDrop High
150 mm²309 A241 A15.14 V (3.78%)384.9 V24.97 V (6.24%)9175.2 WDrop High
185 mm²353 A275 A12.27 V (3.07%)387.7 V20.24 V (5.06%)7439.4 W~ ≤5%
240 mm²415 A324 A9.46 V (2.36%)390.5 V15.6 V (3.9%)5734.5 W✓ OK (≤3%)
300 mm²477 A372 A7.57 V (1.89%)392.4 V12.48 V (3.12%)4587.6 W✓ OK (≤3%)
400 mm²570 A445 A5.68 V (1.42%)394.3 V9.36 V (2.34%)3440.7 W✓ OK (≤3%)

FAQ — Kabelarea för 350 Ampere vid 175 Meter (400V)

Vilken kabelarea krävs för 350A vid 175 meter (400V)?

För 350 Ampere över 175 meter vid 400V rekommenderas 240 mm² kopparkabel för att hålla spänningsfallet under 3% (9.46V / 2.36%).

Hur stor effekt motsvarar 350A vid 400V?

Det motsvarar 242.49 kW med en rekommenderad säkring på 350A.