Kabelarea för 375 Ampere vid 90 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 375 A över 90 m vid 400V.
Copper Cable (≤3% Drop)240 mm²Drop: 5.21V (1.3%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.16V (1.29%)
Voltage at Load394.8 VLine Loss: 3385.5 W
Max Power & Breaker259.81 kW400A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 90m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 833.98 V (208.5%) | 0.0 V | 1375.68 V (343.92%) | 541687.5 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 500.39 V (125.1%) | 0.0 V | 825.41 V (206.35%) | 325012.5 W | Drop High |
| 4 mm² | 32 A | 25 A | 312.74 V (78.19%) | 87.3 V | 515.88 V (128.97%) | 203132.8 W | Drop High |
| 6 mm² | 41 A | 32 A | 208.5 V (52.12%) | 191.5 V | 343.92 V (85.98%) | 135421.9 W | Drop High |
| 10 mm² | 57 A | 44 A | 125.1 V (31.27%) | 274.9 V | 206.35 V (51.59%) | 81253.1 W | Drop High |
| 16 mm² | 76 A | 59 A | 78.19 V (19.55%) | 321.8 V | 128.97 V (32.24%) | 50783.2 W | Drop High |
| 25 mm² | 101 A | 78 A | 50.04 V (12.51%) | 350.0 V | 82.54 V (20.64%) | 32501.2 W | Drop High |
| 35 mm² | 125 A | 97 A | 35.74 V (8.94%) | 364.3 V | 58.96 V (14.74%) | 23215.2 W | Drop High |
| 50 mm² | 151 A | 118 A | 25.02 V (6.25%) | 375.0 V | 41.27 V (10.32%) | 16250.6 W | Drop High |
| 70 mm² | 192 A | 150 A | 17.87 V (4.47%) | 382.1 V | 29.48 V (7.37%) | 11607.6 W | Drop High |
| 95 mm² | 232 A | 181 A | 13.17 V (3.29%) | 386.8 V | 21.72 V (5.43%) | 8553.0 W | Drop High |
| 120 mm² | 269 A | 210 A | 10.42 V (2.61%) | 389.6 V | 17.2 V (4.3%) | 6771.1 W | Drop High |
| 150 mm² | 309 A | 241 A | 8.34 V (2.08%) | 391.7 V | 13.76 V (3.44%) | 5416.9 W | Drop High |
| 185 mm² | 353 A | 275 A | 6.76 V (1.69%) | 393.2 V | 11.15 V (2.79%) | 4392.1 W | Drop High |
| 240 mm² | 415 A | 324 A | 5.21 V (1.3%) | 394.8 V | 8.6 V (2.15%) | 3385.5 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 4.17 V (1.04%) | 395.8 V | 6.88 V (1.72%) | 2708.4 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 3.13 V (0.78%) | 396.9 V | 5.16 V (1.29%) | 2031.3 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 375 Ampere vid 90 Meter (400V)
Vilken kabelarea krävs för 375A vid 90 meter (400V)?
För 375 Ampere över 90 meter vid 400V rekommenderas 240 mm² kopparkabel för att hålla spänningsfallet under 3% (5.21V / 1.3%).
Hur stor effekt motsvarar 375A vid 400V?
Det motsvarar 259.81 kW med en rekommenderad säkring på 400A.
Related Lengths & Currents (400V)
375A · 5m (400V)375A · 10m (400V)375A · 15m (400V)375A · 20m (400V)375A · 25m (400V)375A · 30m (400V)375A · 35m (400V)375A · 40m (400V)375A · 45m (400V)375A · 50m (400V)375A · 60m (400V)375A · 70m (400V)10A · 90m (400V)16A · 90m (400V)20A · 90m (400V)25A · 90m (400V)32A · 90m (400V)40A · 90m (400V)50A · 90m (400V)63A · 90m (400V)80A · 90m (400V)100A · 90m (400V)125A · 90m (400V)160A · 90m (400V)200A · 90m (400V)