Kabelarea för 425 Ampere vid 300 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 425 A över 300 m vid 230V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 6.82V (2.96%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 22.5V (9.78%)
Voltage at Load223.2 VLine Loss: 2899.1 W
Max Power & Breaker97.75 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3638.0 V (1581.74%)0.0 V6001.0 V (2609.13%)1546150.0 WDrop High
2.5 mm²24 A18 A2182.8 V (949.04%)0.0 V3600.6 V (1565.48%)927690.0 WDrop High
4 mm²32 A25 A1364.25 V (593.15%)0.0 V2250.38 V (978.42%)579806.2 WDrop High
6 mm²41 A32 A909.5 V (395.43%)0.0 V1500.25 V (652.28%)386537.5 WDrop High
10 mm²57 A44 A545.7 V (237.26%)0.0 V900.15 V (391.37%)231922.5 WDrop High
16 mm²76 A59 A341.06 V (148.29%)0.0 V562.59 V (244.61%)144951.6 WDrop High
25 mm²101 A78 A218.28 V (94.9%)11.7 V360.06 V (156.55%)92769.0 WDrop High
35 mm²125 A97 A155.91 V (67.79%)74.1 V257.19 V (111.82%)66263.6 WDrop High
50 mm²151 A118 A109.14 V (47.45%)120.9 V180.03 V (78.27%)46384.5 WDrop High
70 mm²192 A150 A77.96 V (33.89%)152.0 V128.59 V (55.91%)33131.8 WDrop High
95 mm²232 A181 A57.44 V (24.97%)172.6 V94.75 V (41.2%)24412.9 WDrop High
120 mm²269 A210 A45.48 V (19.77%)184.5 V75.01 V (32.61%)19326.9 WDrop High
150 mm²309 A241 A36.38 V (15.82%)193.6 V60.01 V (26.09%)15461.5 WDrop High
185 mm²353 A275 A29.5 V (12.82%)200.5 V48.66 V (21.16%)12536.4 WDrop High
240 mm²415 A324 A22.74 V (9.89%)207.3 V37.51 V (16.31%)9663.4 WDrop High
300 mm²477 A372 A18.19 V (7.91%)211.8 V30.0 V (13.05%)7730.8 WDrop High
400 mm²570 A445 A13.64 V (5.93%)216.4 V22.5 V (9.78%)5798.1 WDrop High

FAQ — Kabelarea för 425 Ampere vid 300 Meter (230V)

Vilken kabelarea krävs för 425A vid 300 meter (230V)?

För 425 Ampere över 300 meter vid 230V rekommenderas 2× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (6.82V / 2.96%).

Hur stor effekt motsvarar 425A vid 230V?

Det motsvarar 97.75 kW med en rekommenderad säkring på 450A.