⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 425 Ampere vid 500 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 425 A över 500 m vid 230V.

Copper Cable (≤3% Drop)4× 400 mm²Drop: 5.68V (2.47%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 37.51V (16.31%)
Voltage at Load224.3 VLine Loss: 2415.8 W
Max Power & Breaker97.75 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 500m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A6063.33 V (2636.23%)0.0 V10001.67 V (4348.55%)2576916.7 WDrop High
2.5 mm²24 A18 A3638.0 V (1581.74%)0.0 V6001.0 V (2609.13%)1546150.0 WDrop High
4 mm²32 A25 A2273.75 V (988.59%)0.0 V3750.62 V (1630.71%)966343.7 WDrop High
6 mm²41 A32 A1515.83 V (659.06%)0.0 V2500.42 V (1087.14%)644229.2 WDrop High
10 mm²57 A44 A909.5 V (395.43%)0.0 V1500.25 V (652.28%)386537.5 WDrop High
16 mm²76 A59 A568.44 V (247.15%)0.0 V937.66 V (407.68%)241585.9 WDrop High
25 mm²101 A78 A363.8 V (158.17%)0.0 V600.1 V (260.91%)154615.0 WDrop High
35 mm²125 A97 A259.86 V (112.98%)0.0 V428.64 V (186.37%)110439.3 WDrop High
50 mm²151 A118 A181.9 V (79.09%)48.1 V300.05 V (130.46%)77307.5 WDrop High
70 mm²192 A150 A129.93 V (56.49%)100.1 V214.32 V (93.18%)55219.6 WDrop High
95 mm²232 A181 A95.74 V (41.62%)134.3 V157.92 V (68.66%)40688.2 WDrop High
120 mm²269 A210 A75.79 V (32.95%)154.2 V125.02 V (54.36%)32211.5 WDrop High
150 mm²309 A241 A60.63 V (26.36%)169.4 V100.02 V (43.49%)25769.2 WDrop High
185 mm²353 A275 A49.16 V (21.37%)180.8 V81.09 V (35.26%)20893.9 WDrop High
240 mm²415 A324 A37.9 V (16.48%)192.1 V62.51 V (27.18%)16105.7 WDrop High
300 mm²477 A372 A30.32 V (13.18%)199.7 V50.01 V (21.74%)12884.6 WDrop High
400 mm²570 A445 A22.74 V (9.89%)207.3 V37.51 V (16.31%)9663.4 WDrop High

FAQ — Kabelarea för 425 Ampere vid 500 Meter (230V)

Vilken kabelarea krävs för 425A vid 500 meter (230V)?

För 425 Ampere över 500 meter vid 230V rekommenderas 4× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (5.68V / 2.47%).

Hur stor effekt motsvarar 425A vid 230V?

Det motsvarar 97.75 kW med en rekommenderad säkring på 450A.