⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 5 Ampere vid 20 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 5 A över 20 m vid 400V.

Copper Cable (≤3% Drop)1.5 mm²Drop: 2.47V (0.62%)
Aluminum Cable (≤3% Drop)1.5 mm²Drop: 4.08V (1.02%)
Voltage at Load397.5 VLine Loss: 21.4 W
Max Power & Breaker3.46 kW6A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 5A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2.47 V (0.62%)397.5 V4.08 V (1.02%)21.4 W✓ OK (≤3%)
2.5 mm²24 A18 A1.48 V (0.37%)398.5 V2.45 V (0.61%)12.8 W✓ OK (≤3%)
4 mm²32 A25 A0.93 V (0.23%)399.1 V1.53 V (0.38%)8.0 W✓ OK (≤3%)
6 mm²41 A32 A0.62 V (0.15%)399.4 V1.02 V (0.25%)5.3 W✓ OK (≤3%)
10 mm²57 A44 A0.37 V (0.09%)399.6 V0.61 V (0.15%)3.2 W✓ OK (≤3%)
16 mm²76 A59 A0.23 V (0.06%)399.8 V0.38 V (0.1%)2.0 W✓ OK (≤3%)
25 mm²101 A78 A0.15 V (0.04%)399.9 V0.24 V (0.06%)1.3 W✓ OK (≤3%)
35 mm²125 A97 A0.11 V (0.03%)399.9 V0.17 V (0.04%)0.9 W✓ OK (≤3%)
50 mm²151 A118 A0.07 V (0.02%)399.9 V0.12 V (0.03%)0.6 W✓ OK (≤3%)
70 mm²192 A150 A0.05 V (0.01%)399.9 V0.09 V (0.02%)0.5 W✓ OK (≤3%)
95 mm²232 A181 A0.04 V (0.01%)400.0 V0.06 V (0.02%)0.3 W✓ OK (≤3%)
120 mm²269 A210 A0.03 V (0.01%)400.0 V0.05 V (0.01%)0.3 W✓ OK (≤3%)
150 mm²309 A241 A0.02 V (0.01%)400.0 V0.04 V (0.01%)0.2 W✓ OK (≤3%)
185 mm²353 A275 A0.02 V (0.01%)400.0 V0.03 V (0.01%)0.2 W✓ OK (≤3%)
240 mm²415 A324 A0.02 V (0.0%)400.0 V0.03 V (0.01%)0.1 W✓ OK (≤3%)
300 mm²477 A372 A0.01 V (0.0%)400.0 V0.02 V (0.01%)0.1 W✓ OK (≤3%)
400 mm²570 A445 A0.01 V (0.0%)400.0 V0.02 V (0.0%)0.1 W✓ OK (≤3%)

FAQ — Kabelarea för 5 Ampere vid 20 Meter (400V)

Vilken kabelarea krävs för 5A vid 20 meter (400V)?

För 5 Ampere över 20 meter vid 400V rekommenderas 1.5 mm² kopparkabel för att hålla spänningsfallet under 3% (2.47V / 0.62%).

Hur stor effekt motsvarar 5A vid 400V?

Det motsvarar 3.46 kW med en rekommenderad säkring på 6A.