Kabelarea för 5 Ampere vid 50 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 5 A över 50 m vid 400V.

Copper Cable (≤3% Drop)1.5 mm²Drop: 6.18V (1.54%)
Aluminum Cable (≤3% Drop)1.5 mm²Drop: 10.19V (2.55%)
Voltage at Load393.8 VLine Loss: 53.5 W
Max Power & Breaker3.46 kW6A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 5A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A6.18 V (1.54%)393.8 V10.19 V (2.55%)53.5 W✓ OK (≤3%)
2.5 mm²24 A18 A3.71 V (0.93%)396.3 V6.11 V (1.53%)32.1 W✓ OK (≤3%)
4 mm²32 A25 A2.32 V (0.58%)397.7 V3.82 V (0.96%)20.1 W✓ OK (≤3%)
6 mm²41 A32 A1.54 V (0.39%)398.5 V2.55 V (0.64%)13.4 W✓ OK (≤3%)
10 mm²57 A44 A0.93 V (0.23%)399.1 V1.53 V (0.38%)8.0 W✓ OK (≤3%)
16 mm²76 A59 A0.58 V (0.14%)399.4 V0.96 V (0.24%)5.0 W✓ OK (≤3%)
25 mm²101 A78 A0.37 V (0.09%)399.6 V0.61 V (0.15%)3.2 W✓ OK (≤3%)
35 mm²125 A97 A0.26 V (0.07%)399.7 V0.44 V (0.11%)2.3 W✓ OK (≤3%)
50 mm²151 A118 A0.19 V (0.05%)399.8 V0.31 V (0.08%)1.6 W✓ OK (≤3%)
70 mm²192 A150 A0.13 V (0.03%)399.9 V0.22 V (0.05%)1.1 W✓ OK (≤3%)
95 mm²232 A181 A0.1 V (0.02%)399.9 V0.16 V (0.04%)0.8 W✓ OK (≤3%)
120 mm²269 A210 A0.08 V (0.02%)399.9 V0.13 V (0.03%)0.7 W✓ OK (≤3%)
150 mm²309 A241 A0.06 V (0.02%)399.9 V0.1 V (0.03%)0.5 W✓ OK (≤3%)
185 mm²353 A275 A0.05 V (0.01%)399.9 V0.08 V (0.02%)0.4 W✓ OK (≤3%)
240 mm²415 A324 A0.04 V (0.01%)400.0 V0.06 V (0.02%)0.3 W✓ OK (≤3%)
300 mm²477 A372 A0.03 V (0.01%)400.0 V0.05 V (0.01%)0.3 W✓ OK (≤3%)
400 mm²570 A445 A0.02 V (0.01%)400.0 V0.04 V (0.01%)0.2 W✓ OK (≤3%)

FAQ — Kabelarea för 5 Ampere vid 50 Meter (400V)

Vilken kabelarea krävs för 5A vid 50 meter (400V)?

För 5 Ampere över 50 meter vid 400V rekommenderas 1.5 mm² kopparkabel för att hålla spänningsfallet under 3% (6.18V / 1.54%).

Hur stor effekt motsvarar 5A vid 400V?

Det motsvarar 3.46 kW med en rekommenderad säkring på 6A.