Kabelarea för 5 Ampere vid 25 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 5 A över 25 m vid 400V.

Copper Cable (≤3% Drop)1.5 mm²Drop: 3.09V (0.77%)
Aluminum Cable (≤3% Drop)1.5 mm²Drop: 5.1V (1.27%)
Voltage at Load396.9 VLine Loss: 26.7 W
Max Power & Breaker3.46 kW6A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 5A at 25m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3.09 V (0.77%)396.9 V5.1 V (1.27%)26.7 W✓ OK (≤3%)
2.5 mm²24 A18 A1.85 V (0.46%)398.1 V3.06 V (0.76%)16.0 W✓ OK (≤3%)
4 mm²32 A25 A1.16 V (0.29%)398.8 V1.91 V (0.48%)10.0 W✓ OK (≤3%)
6 mm²41 A32 A0.77 V (0.19%)399.2 V1.27 V (0.32%)6.7 W✓ OK (≤3%)
10 mm²57 A44 A0.46 V (0.12%)399.5 V0.76 V (0.19%)4.0 W✓ OK (≤3%)
16 mm²76 A59 A0.29 V (0.07%)399.7 V0.48 V (0.12%)2.5 W✓ OK (≤3%)
25 mm²101 A78 A0.19 V (0.05%)399.8 V0.31 V (0.08%)1.6 W✓ OK (≤3%)
35 mm²125 A97 A0.13 V (0.03%)399.9 V0.22 V (0.05%)1.1 W✓ OK (≤3%)
50 mm²151 A118 A0.09 V (0.02%)399.9 V0.15 V (0.04%)0.8 W✓ OK (≤3%)
70 mm²192 A150 A0.07 V (0.02%)399.9 V0.11 V (0.03%)0.6 W✓ OK (≤3%)
95 mm²232 A181 A0.05 V (0.01%)400.0 V0.08 V (0.02%)0.4 W✓ OK (≤3%)
120 mm²269 A210 A0.04 V (0.01%)400.0 V0.06 V (0.02%)0.3 W✓ OK (≤3%)
150 mm²309 A241 A0.03 V (0.01%)400.0 V0.05 V (0.01%)0.3 W✓ OK (≤3%)
185 mm²353 A275 A0.03 V (0.01%)400.0 V0.04 V (0.01%)0.2 W✓ OK (≤3%)
240 mm²415 A324 A0.02 V (0.0%)400.0 V0.03 V (0.01%)0.2 W✓ OK (≤3%)
300 mm²477 A372 A0.02 V (0.0%)400.0 V0.03 V (0.01%)0.1 W✓ OK (≤3%)
400 mm²570 A445 A0.01 V (0.0%)400.0 V0.02 V (0.0%)0.1 W✓ OK (≤3%)

FAQ — Kabelarea för 5 Ampere vid 25 Meter (400V)

Vilken kabelarea krävs för 5A vid 25 meter (400V)?

För 5 Ampere över 25 meter vid 400V rekommenderas 1.5 mm² kopparkabel för att hålla spänningsfallet under 3% (3.09V / 0.77%).

Hur stor effekt motsvarar 5A vid 400V?

Det motsvarar 3.46 kW med en rekommenderad säkring på 6A.